Specifications
SX-1115-RT
TECHNICAL DESCRIPTION
The Powerframe 420 shall be housed in a magnetic shielding NEMA
steel enclosure. It shall operate from 120 volts AC and have a barrier
strip accessible through knock-outs in the enclosure for hardwiring
power input and output connections. Overall dimensions shall be
16.0" H x 12.0" W x 4.0" D. Weight shall be 30 pounds. The
Powerframe 420 shall have a load rating of 20 amps per circuit at 120
volts (80 amps total), a self-test circuit with visual indicator, and
provide EMI/RFI filtering. It shall withstand at least 1000 occurrences
of surge pulse voltages up to 6000 volts.
PF-420
surgex.com
v1.0
© 2018 AMETEK Electronic Systems Protection. All rights reserved.
BRANCH CIRCUIT
PF420
20A (x4)
120V
4 W
0 Volts
6000 Volts *
Unlimited (due to current limiting) *
Unlimited (due to current limiting) *
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000
1RUPDOPRGHORDG
> 20 dB, 39 kHz – 50 MHz
> 30 dB, 150 kHz – 50 MHz
25 dB @ 100 kHz; 45 dB @ 300 kHz;
67 dB @ 3 MHz; 35 dB @ 30 MHz
&RPPRQ0RGHORDG
> 10 dB, 290 kHz – 50 MHz
> 20 dB, 1.9 MHz - 7.875 MHz
> 30 dB, 4.2 MHz – 5.125 MHz
10 dB @ 300 kHz; 17 dB @ 1 MHz;
30 dB @ 5 MHz; 14 dB @ 20 MHz
No
No
None
None
Voltage NA
Current NA
Power NA
Energy NA
Temperature NA
No
None
None
No
No
16.0" H x 12.0" W x 4.0" D
30 lbs
5C to 35C
5% to 95% R.H. Non-condensing
Conforms to UL Std 1283
Certified to CSA Std C22.2 No. 8
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
** Specifications subject to change without notice
SPECS v.030118
Agency Listings
Over-Temperature Auto Shutdown
Measurement
Accuracy
Network Port
Serial Port
Temperature Sensor Input
Humidity Range
Auxiliary Relay Outputs
Contact Closure Input
Dimensions
Weight
Temperature Range:
SPECIFICATIONS
Voltage Rating
Over-Current Auto Shutdown
Load Rating
Power Requirement (no load)
Surge Let-through Voltage (6000 Volt Surge)
Maximum Applied Surge Voltage
Maximum Applied Surge Current
Maximum Applied Surge Energy
Endurance (C62.41-1991 category B3 pulses)
EMI/RFI Filter
Under-Voltage Auto Shutdown
Over-Voltage Auto Shutdown
PF-420
Advanced Series Mode
®
Surge Eliminator / Power Conditioner
BRANCH CIRCUIT
SELF-TEST
SELF-TEST
SELF-TEST
SELF-TEST
DOOR
16.30
DOOR12.30
16.00
12.00
11.00
13.00
4.18
.50
1.50
KO DIAMETER QTY
A 1.375 8
SCALE: .300/1.000
THIS DRAWING IS FOR REFERENCE
J.J. 10/4/06
A
A
A
A
A
A
A
A
KNOCKOUT DIAMETER
SEE TABLE
Ø,280 X4 HOLES
WALL MOUNT
REV.
SHEET
DRAWING NO.PROJECT
PAPER
SCALE
TOLERANCES
UNLESS NOTED
MATERIAL
FINISH
REVISIONS
REV
DATE
DESCRIPTION
BY
B
.XXX ±.005 .XX ±.01 .X ±.02 ANGULAR ±0.5°
APPROVAL
DATE
DRAWN
CHK
APPV
APPV
CAD
FILE NAME
DISK NAME
DRAWING NO.
REV.
ENCLOSURE OUTLINE, NEMA 16X14X4 PWR FRAME 420
v1.0
© 2018 AMETEK Electronic Systems Protection. All rights reserved.