Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a
door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying
attention to the direction of the diode.
Do not connect the relay of the Input Module in duplicate to the device connected to the relay port of the
master device.
Supervised Input Connection
You can connect a fire sensor, heat sensor, security sensor, door sensor, exit button, or etc. The SUPERVISED INPUT 0
to 11 pins detect the voltage flowing through the circuit to monitor device disconnection, short, on, and off conditions,
and can also be used as a general TTL input. With BioStar 2, you can set the behavior according to the Supervised Input
status, and you can monitor the status of each input.
EMERGENCY
Do not connect the input of the Input Module in duplicate to the device connected to the input port of the
master device.
The Input Module can be used by connecting 1 kΩ, 2.2 kΩ, 4.7 kΩ, or 10 kΩ resistors. After connecting the
resistor corresponding to the input device of the connection, set the same resistance value in BioStar 2.
To learn how to operate it depending on the supervised input status, refer to the manual of BioStar 2.