Channel Nuts
UC-100 Universal Cone Nut
Eliminates the inventory and installation hassles of conventional spring nuts.
Fits all 1
5
8" channel, regardless of depth, with a simple twist of your thumb.
Pliable nylon cone secures the nut in place through the entire range of
construction site temperatures.
Screw Threads
THREAD SIZE (IN.)
1
4
3
8
1
2
THREADS PER INCH 20 16 13
DESIGN TORQUE (FT.–LBS.) 6 19 50
Standard Finish – GoldGalv
®
, unless otherwise stated.
All threaded products are American Standard thread, free fit class 2.
GoldGalv
®
hardware finish is standard for all Superstrut
®
products.
This is a multi-process finish of electro-plated zinc, followed by gold-
colored trivalent chromium to give excellent corrosion resistance and a
superior paint base. See pages B-106–B-107 for a complete description
of the GoldGalv
®
hardware finish.
Note: Standard Spring and Springless Nuts are supplied with a silver electro-galvanized (EG)
finish. These items are not visible in a gold system and are universal with other systems’
finishes and colorations.
Superstrut
®
channel nuts are manufactured from mild steel
and are case hardened.
Design Data
Superstrut
®
self-aligning channel nuts are designed to provide resistance
to pull out and resistance to side slip in excess of the full strength of the
channels with which they are used. The extreme resistance to side slip
results from the unique design of the alternate teeth, spaced and designed
to develop a wedging action that increases with pressure or load.
Load Ratings for
1
4
",
3
8
" and
1
2
" Strut Nuts used in Superstrut
®
CHANNEL NUT
SIZES (IN.)
SLIP TEST
RATING PULL TEST RATING
1
4 300 500
3
8 750 1,000
1
2 1,200 2,000
If connections will be subjected to dynamic or seismic loading conditions,
contact the factory for design assistance.
1. All ratings have safety factor of 3 applied.
2. Load ratings are for Static Applications.