Connection & Query Status
Alarm Parameter Configuration
Completion
Figure 8-2 EU-E Debugging Procedures
8.1. Network Management System Setup for SNMP
CrossFire system supports Network Management System (NMS) for monitoring the whole system. Each
slave devices in system is assigned a unique Site ID automatically by Master AU while Master AU Site ID is
default as Device IP Addr in LAN Connectivity on AU WebOMT. The NMS supports SNMP and UDP
protocol. According to selected protocol, configure corresponding parameters as shown in Table 4-6.
The following procedure is setup for MIB Browser of SNMP:
1. Get wired access to OMT on Master AU as Section 3.2.1
2. Get into LAN Connectivity Under Settings
3. Set parameter for SNMP (See Figure 8-3):
a. Select SNMP in Protocol dropdown.
b. Set PC or monitor device IP address information in NMS IP Addr and NMS port.
c. Set trap PC or monitor device IP address information in Trap IP Addr1 and Trap port, if it supports
trap functionality.
d. Click Set in pop-up window.
4. Open MIB Browser to monitor the whole system.