Brochure
I N T E R I O R S L A B H E A T I N G C A B L E
Technical
– Installation Design Manual
– Product Submittal
– Powerpoint
– Website
Support Materials
SlabHeat Cable is a complete heating cable consisting of a series
resistance heating cable and a single power lead for easy single-point
connection. The heating cable length cannot be cut to fit.
SlabHeat Cables are available in various lengths with
voltage options of 120 and 240VAC.
Application
SlabHeat cables are designed for use only in an interior space embedded
in concrete.
SlabHeat
™
Cable
Electric Indoor Heating Cable
ES-ST-SlabHeat-Cable
For Residential and Commercial Applications
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
–––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
UL Listed for U.S. under UL Standard 1673 and
Canada under CAN/CSA C22.2 No. 130-03.
Listing file number E185866.
ATTENTION: Never cut the heating cable or damage
it in any way. Use only the attachment methods as
described in the Installation Manual to fasten the
SlabHeat cable to the floor, as other methods may
damage the heating cable.
This Engineering Sheet is not meant to provide full
installation instructions. In order to avoid property damage
or injury, please refer to the complete installation manual
and warnings provided with the product.
Watts Radiant product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please
contact Watts Radiant Technical Service. Watts Radiant reserves the right to change or modify product design, construction, specifications, or materials without
prior notice and without incurring any obligation to make such changes and modifications on Watts Radiant products previously or subsequently sold.
Specifications
Supply Voltage
120VAC, 1-phase
240VAC, 1-phase
Maximum Heater Current 15 Amps
Maximum Circuit Load* 15 Amps
Wire Spacing
4"
6"
Power Lead 10' long, 14 ga.
*GFCI (Ground Fault Circuit Interrupter) is required for each circuit.
Application Parameters
Min. Bend Radius 1 inch
Max. Exposure Temperature
(continuous and storage)
194ºF (90ºC)
Min. Installation Temperature 50ºF (10ºC)
Heating Density
120VAC 240VAC
4" Wire
Spacing
15 W/sf
51 BTUh/sf
6" Wire
Spacing
10 W/sf
34 BTUh/sf
Installation Parameters
Determine a time to install the cable when equipment, heavy tools, and
site traffic will be minimal. Apply the surfacing courses over the cable the
same day the cable is installed.
If installing cable in the upper layer of a two-stage concrete slab, the
cable should be completely ready for the second stage. There is limited
time between stages, as the slab should not be allowed to fully cure.
Therefore, lay out the cable and tie it to rewire that can be quickly lifted
into place after the first stage is laid.
Inspect the area and remove any sharp objects.
Install in temperatures at least 50°F (10°C).
For a new concrete slab, when a run of cable exceeds 20 feet, an
additional downward U-shaped loop with a 1 to 2 inch radius, should
be added to help minimize possible damage to the cable from thermal
expansion.
Polyurethane Outer Jacket
Dual Copper Heating Elements
Full Coverage Braided
Copper Ground Plane
ETFE Insulation
Foil Shield
Product
Submittal
Please note that local codes may require this product and/or the control to be installed or connected by an electrician.
Series SH
Installation Manual
Installation
Design
Manual
PowerPoint
Website
www.suntouch.com/slabheat
Page 6
USA: 4500 East Progress Place, Springfield, MO 65803; www.suntouch.com
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.suntouch.com
F-ST-SlabHeat-Product-Information 1111 © 2011 Watts Radiant