SlabHeat Installation Manual

15
Problem
Cable resistance
measurement is outside
the range printed on the
nameplate label.
Floor does not get warm.
Floor heats continuously.
Floor temperature shows
much higher than what the
floor feels like.
Control is not working
correctly.
Control is not working
at all.
GFCI conflicts and
false-trips.
Troubleshooting Guide
If problems with the system arise, please consult the troubleshooting guide below. Any troubleshooting work
should be done with the power removed from the circuit, unless otherwise indicated. An electrician should
perform any troubleshooting involving wiring, connections, and testing that requires power to be applied.
Possible Cause
An analog ohmmeter (using a moving
needle) was used to take the reading.
If measurement shows an open or short
circuit, the cable has been damaged.
If measurement is just a little low or high, room
temperature has affected the resistance.
The resistance measurement could be from
more than one cable wired in series, or wired
in parallel. Either will provide false resistance
readings.
The ohmmeter may be set to the wrong
scale. For instance, the 200 K ohms scale
measures up to 200,000 ohms.
Cable has been damaged.
GFCI has tripped, indicated by a light on the
control or “GFCI TRIP”.
Incorrect voltage supplied, or mismatched
electrical components used.
Cables are wired in “series or daisy chained”
(end-to-end).
Incorrect wiring. The control was “bypassed”
when it was wired to the power supply.
Defective control.
Floor sensor is not wired properly, or is located
incorrectly.
If a programmable control, the programming
may be incorrect.
Incorrect voltage supplied, or mismatched
components used.
Floor sensor is not wired properly, or is not
working properly.
Loose connection(s) on line side and/or load
side of control.
Defective control.
No power is supplied.
Floor sensor is not wired properly, or is not
working properly.
Defective control.
An electric motor or a ballasted light source is
sharing the circuit with the cable(s).
Solution
Obtain a digital ohmmeter able to read 0 to 20,000 ohms and
remeasure the resistance.
Record resistances between all wires and contact the manufacturer.
Make the room temperature 65°–75°F, or contact the manufacturer.
Make sure resistance measurements are for only one cable at
a time. When connecting more than one cable to the control,
multiple cable must be wired in parallel.
The ohmmeter should typically be set to the 200 ohms scale, with
the exception of cables having a rating above 200 ohms on their
nameplate label. If the resistance reading is outside the range
printed on the nameplate label, contact the manufacturer.
Measure cable resistance. Check for both open circuit” and “short
circuit” as detailed earlier in this manual. If damaged, record
resistances between all wires and contact the manufacturer.
Check for loose wire connections. Reset the GFCI on the control
or circuit breaker. If it trips again, check for a short circuit in the
cable as detailed earlier in this manual. If cable is damaged,
record resistances between all wires and contact the manufacturer.
If cable is not damaged, replace the GFCI control. Also see “GFCI
conflicts” below.
Measure line voltage, 120V cable have Yellow tags marked "120V"
and 240V cables have Red tags marked "240V".
Multiple cables must be connected in “parallel” .
Make sure wiring connections are correct. Consult the wiring
diagram on the back of the control, the instructions that came
with the control, or the wiring diagrams in Appendix 2.
Return control to dealer for replacement.
Make sure only one floor sensor is connected to the control.
Carefully read and follow control programming instructions.
Test voltage, verify parts. See “Incorrect voltage supplied” above.
Make sure only one floor sensor is connected to the control.
Remove and reinstall the wire nuts at each connection. Make sure
the wire nuts are tight. Check all connections back to the breaker.
Return control to dealer for replacement.
Check circuit breaker. Measure voltage at the control. Check all
connections between breaker and control.
Make sure only one floor sensor is connected to the control.
Return control to dealer for replacement.
Electric motors and other electrical devices can cause a GFCI to
false-trip. Run a dedicated circuit to the floor-warming system.