Contactor Pro Owner's Manual
For ProMelt CP-50, CP-100, and CP-200
Panels
The CP-50, CP-100, and CP-200 are turn-key panels for activating a
ProMelt snow melting system when used in conjunction with the ProMelt
series of controls. They allow simple connection from the circuit breaker
panel and have a manual override timer and heating indicator. Any CP
series panel can be used as an "extension" panel that connects to
another CP series panel and allows additional circuits to be controlled.
Specifications
Features
Each ProMelt system can be used with a wide variety of
moisture/precipitation sensors, including the following:
Slab Mounted: PM-HSC5
Pole/wall Mounted: PM-224 and PM-824
Each sensor option is designed to operate a single system.
Use a dedicated sensor and CP panel group for each snow melt zone.
CP series of panels can be used directly with any ProMelt cable or
mat system. Power is connected directly to each contactor in the panel.
It is pre-wired to the included transformer, terminal blocks, and the coil
terminals on the provided contactors. It is not recommended to unwire,
or tamper with existing wiring without pre-authorization from the factory.
ProMelt
®
Contactor Pro Relay Panels
The ProMelt Contactor Pro Relay Panel is available in three configurations:
CP-50 (single contactor), CP-100 (dual contactors), and CP-200 (quad
contactors). Each ProMelt CP series panel is a NEMA Type 1 for mounting
indoors on a wall with knockouts for conduit.
!
WARNING: General Safety Instructions
1. THIS UNIT SHOULD BE INSTALLED ONLY BY
QUALIFIED PERSONNEL!
2. Disconnect all power from the control before
opening the front cover plate.
CP-50, CP-100, CP-200 Specifications
Terminals Wiring Type
L1, L2
T1, T2
120, 208, 240, 277 VAC
12 AWG
(Minimum)
PM Class 2,
18-24 AWG
(See sensor
instructions for
size and length
limits)
24VAC, COMMON 24 VAC
X1, X2 Dry Contact, N.O.
Compatible
Sensors
PM-224
PM-824
PM-HSC5
ETL Listing
File 3176880,
UL 508A,
CAN/CSA-C22.2 No. 14
Environment
Indoor, NEMA 1 enclosure,
operating temperature
0ºF to 100ºF (-18ºC to 38ºC)
For Residential and Commercial Snow Melt Applications
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
–––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
!
CAUTION
This Engineering Sheet is not intended to provide full installation
instructions and safety information. In order to avoid property
damage or injury, please refer to the complete installation manual
and product safety information provided with the product.
Watts Radiant product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please
contact Watts Radiant Technical Service. Watts Radiant reserves the right to change or modify product design, construction, specifications, or materials without
prior notice and without incurring any obligation to make such changes and modifications on Watts Radiant products previously or subsequently sold.
ES-ST-ProMelt-Contactor-Pro
√ Description Order # Dimensions
Contactor Pro CP-50 81012215 12" x 12" x 4"
Contactor Pro CP-100 81012216 12" x 12" x 4"
Contactor Pro CP-200 81012217 12" x 12" x 4"