Product Overview
PUMP DIMENSIONS
We reserve the right to change specications without prior notice.
A2VA-3006B - US - Ed. 4 - Jan 2020
Inlet
Nozzle outlet
Pressure adjustment
Bleeder valve
Cone valveReturn
Internal by-pass plug
TECHNICAL DATA
General
Mounting Flange mounting
Connection threads
Inlet
Nozzle outlet
Pressure gauge port
Bleeder valve port
1/4 NPTF
1/8 NPTF
1/8 NPTF
1/8 NPTF
Valve function Pressure regulation and cut-off (cut-off
only assured for specied pressure
range
Cut-off Diaphragm and solenoid
Strainer 3 GPH
Shaft 5/16 in
By-pass plug Not inserted in return port, for one
pipe system.To be inserted in return
port with a 5/32 Allen key for two-pipe
system.
Nozzle pressure range 100 - 200 psi
Delivery pressure setting 100 psi
Rated nozzle ow 4 GPH @100 psi, 3450 rpm (#1, #2
and B6-B20 fuel)
3 GPH @200 psi, 3450 rpm (#2 and
B6-B20 fuel)
Oil temperature 50 - 115 F
Inlet and return pressures 10 psi max.
NFPA limits pressures to 3 psi max
Suction height Single pipe : 6" Hg max. vacuum,
Two-pipe : 12" Hg max. vacuum, to
prevent air separation from oil
Power consumption 70 W @100 psi
90 W @150 psi
Rated speed 3450 rpm max.
Recommended motor
frequency
60 Hz
Hydraulic data
Solenoid valve voltage 110-120 V ; 50/60 Hz
Consumption 9 W
Ambient temperature 50 - 115 F
Maximum pressure 200 psi
Solenoid valve characteristics