Product Manual
Form #43471010
Mar 09 -31-
Call for heat ends and
the heater shuts off?
Yes
No
Troubleshooting ends.
Thermostat is not
working properly.
Replace it if
necessary.
Is the green light still
on?
Yes
No
Turn off gas &
electricity
immediately.
Replace the gas
valve.
Remove valve lead at
ignition module. Does
valve close?
No
Yes
Recheck thermostat
and wiring.
Troubleshooting
continued from the
previous page.
Troubleshooting
continued from the
previous page.
Check the spark gap.
Is it 3/16?
No
Yes
Adjust the spark gap
to 3/16.
Has all the air been
purged from the gas
supply lines?
No
Yes
Purge the gas supply
line.
Check the inlet
pressure to the gas
valve. Is it between
minimum and
maximum for the gas
type?
No
Yes
Adjust supply gas
pressure.
Restart
troubleshooting.
Check the manifold
gas pressure during
startup. Is it zero
inches?
Yes
No
Replace gas valve.
After an initial step
opening, is the
manifold gas pressure
correct?
No
Yes
Adjust manifold gas
pressure. Restart
troubleshooting.
Call factory for
assistance.
Check orifice and
holder for blockage
(i.e. spider web). Is
there any blockage?
Yes
No
Clear blockage.