MINIMUM CLEARANCES TO COMBUSTIBLES
© Copyright 2001, SunStar Heating Products, Inc. 50510M Form No. R104
DISTRIBUTED BY
DIMENSIONS
COMBUSTION AIR AND VENTILATION
Combustion air and venting requirements for all gas-fired heating equipment must be provided per the National Fuel Gas Code NFPA54 and CAN B149 or
the authority having jurisdiction over the installation. Refer to Installation and Operation Instructions for further information. An indirect vented installation
requires a minimum ventilation flow of 4 CFM per 1000 Btu/hr of total installed heater capacity on natural gas by either gravity or power ventilation (4.18
CFM per 1000 Btu/hr on propane). For indirect vented applications, building exhaust openings must be located above the level of the heaters and the inlet
air openings must be located below the level of the heaters.
FOR YOUR SAFETY
OPERATE SUNSTAR GAS INFRARED HEATERS WITH PROPER CARE AND OBSERVE ALL SAFETY PRECAUTIONS. Installation and service must
be performed by a licensed contractor. The installation must conform with local codes. In the absence of local codes, the installation must conform with the
National Fuel Gas Code ANSI Z223.1 (latest edition also known as NFPA 54) or CAN B149 installation codes (latest edition). These codes are available from
ANSI, 1430 Broadway, New York, NY 10018, the National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269 or C.S.A. 55 Scarsdale
Road, Toronto, Ontario M3B 2R3 Canada.
T
ECHNICAL SPECIFICATIONS
SSuunnSSttaarr
®
INFRARED GAS HEATERS
306 West Tremont Avenue
P.O. Box 36271
Charlotte, North Carolina 28236
Telephone (Toll Free): 1(888)778-6782
Telephone (704) 372-3486
Fax: (704) 332-5843
Email: info@sunstarheaters.com
www.sunstarheaters.com
SunStar Heating Products, Inc. strives to improve quality and performance on a continuing basis and reserves the right to change specifications and materials without notice.
We Make Winters Warmer
Heating Products, Inc.
S
G3-N
SG3-L
SG4-N
SG6-N
SG10-N
SG6-L
SG8-N
SG10-L
S
G12-N
S
G13-L
SG14-N
SG15-N
1
1
1
2
2
2
3
3
3
4
4
4
12
1
2
12
13
1
3
1
4
15
15
1
6
17
1
7
18
Natural Gas
Propane Gas
6” 7” 14”
1
4”11”10”
Ignition Type: Direct Spark Ignition
Supply Voltage: 115 Volt
Amp Draw: 0.40 Amp
Gas Connection: 1/2” NPT Female
M
odel
Input
Btu/hr
No. of
Burners
Minimum
Mounting
Height (Feet)
Gas
Type
Gas Type
Burner
Pressure
(
water column)
Supply Pressure
(water column)
Minimum
M
aximum
Mounted at 30∞ AngleMounted Horizontally
Model
S
ides
Ceiling
B
elow
w
/ Reflector
E
xtension
w
/ Reflector
E
xtension
B
elow Front Rear
w
/ Reflector
E
xtension
*Minimum mounting angle of 10 degrees. Observe all required clearances as shown. Clearances are measured from the reflector edge.
SG3 and SG4
SG6 and SG8
SG10 and SG12
SG13, SG14 and SG15 *
31” 37” 73” 101” 73” 101” 37” 51” 31”
49” 49” 99” 138”
99” 138” 49” 69” 37”
49” 65” 129” 181”
129” 181” 61” 85” 49”
49” 65” 137” 191” 137” 191” 65” 91” 49”
END VIEW DIMENSIONS
SIDE VIEW DIMENSIONS
Model
SG3
S
G4
SG6
SG8
SG10
SG12
SG13 SG14
SG15
A
9
”
14
7
/8”
20
3
/4”
26
5
/8”
B
15
3
/4”
21
5
/8”
27
1
/2”
33
3
/8”
26
1
/2”
3
/8” Dia.
Hole for Hanging
(Typical 4 Places)
Optional
Reflector
Extension
Standard
Reflector
A
B
C
C
17
3
/4”
23
5
/8”
23
1
/2”
35
3
/8”
28
1
/2”
7
3
/4”
9
3
/4”
12”