Instruction Guide
Sunpak® Infrared Heaters
9
Ventilation
1. It is required that areas above the heater be
properly vented to allow for necessary
combustion air and removal of combustion gases.
2. Heaters shall be provided with natural or
mechanical means to supply and exhaust at least
4 cfm per 1,000 BTU per hour of heater input.
Exhaust opening for removing the flue products
shall be above the level of the heaters.
3. Heater ventilation must comply with state and
local codes. Never use heater in enclosed area.
Fire Sprinklers
Fire Sprinklers must be located at an appropriate
distance from each heater to avoid accidental activation
of the sprinkler. Ethylene glycol or propylene glycol must
never be used in fire sprinkler systems where heaters are
present as these substances may become flammable
when heated. A fire sprinkler professional must be
consulted when heaters are installed where fire sprinklers
are present to insure that heaters and the fire sprinkler
system are properly integrated. Specific guidelines can be
found in NFPA 13 regarding design and specifications for
Fire Sprinkler Systems near heaters.
Initial Start-Up Procedure
(Read entire Procedure First)
1. Before turning ON your new heater make sure:
a. Heater is securely mounted and clearances from
combustible materials have been observed (see
Clearances – page 7);
b. Tip angle of heater does not exceed 30 degrees
(see Correct Mounting – page 12);
c. Gas line is properly connected and there are no
leaks (see Gas Piping – page 8);
d. Power adapter (7.5 VDC) is connected to a live
power outlet and connected properly to the
heater (see Electrical – page 8 and Basic Wiring
– page 10)
2. Start Heater;
a. Turn ON manual gas valve..
b. Genially press the ON button of the remote
control for 1 second;
c. Allow heater 5 minutes to full warm up. (in full
daylight it may be difficult to see the flame);
d. If heater locks out, press the OFF Button to
RESET Heater and repeat start up sequence.
e. If the heater locks out several times there may
still be air in the gas line.
NOTE: Some white smoke may appear
during or just after the initial start-up of the
heater. White smoke will dissipate with
proceeding use. This is normal due to
some residual lubricate on a new heater
Regular Service and Maintenance
Overtime,particularlyduringlongperiodsofnon‐use,
theheatercanaccumulate dirt anddebrisinand
aroundthepilotandtheburner.Routinemaintenance
shouldbeperformedatleastonceayearbyaqualified
serviceagencytoinsuretheheaterisoperating
properly.Morefrequentservicemay
berequiredfor
heaterslocatednearwaterfronts.Iflocalserviceisnot
availablecallyournaturalgasorpropanesupplier.
Battery Life
Boththewallcontrolandhandheldremotesuse
batteriesavailableatthelocalhardwarestore.Please
keepinmindthefollowing:
• Weak batteries can reduce the range of the
transmitter.
• Batteries should be removed if heaters are not to
be used for a long period of time.
• Dispose of used batteries properly.
• Replace batteries annually or as needed.
Two #2032 Button Batteries power the wall control transmitter They
are available at your local hardware store
.
Loss of Programming
Although each heater comes pre-programmed for two
devices, this programming can be lost if the following
occurs:
• ElectricalPowerSurge
• Heaterisdisconnectedalongperiodoftime.
• Morethanthreedeviceshavebeenprogrammedfor
theheater.