Data Sheet
建 準 電 機 
SUNONWEALTH 
Page 10 of 14 
4. RATED SPEED 
Measured after continuous 10 minute operation at rated voltage in clean air 
( STATIC PRESSURE=0), and at ambient temperature of 25 degrees C under shaft 
horizontal condition. 
5. STARTING VOLTAGE 
Measured the voltage which enables to start the fan in the clean air (static pressure = 0 ) 
by switching on at the voltage under shaft horizontal condition. It is not at continuously 
increasing voltage adjustment. 
6. LOCKED ROTOR CURRENT 
Measured immediately after the fan blade is locked. 
7. AIR FLOW AND STATIC PRESSURE 
The performance specification of air flow and static pressure shown in this specification for 
approval is measured using the exhaust method. A double chamber is used in accordance 
with AMCA 210 standard or DIN 24163 specification . The values are recorded when the 
fan speed has stabilized at rated voltage. 
8. INSULATION RESISTANCE 
1. PLASTIC HOUSING:  
(1) Measured between internal stator and lead wire(+). 
(2) Measured between housing and lead wire(+). 
2. ALUMINIUM HOUSING:  
Measured between internal stator and lead wire(+). 
9. DIELECTRIC STRENGTH 
Measure between housing and lead wire(+). 
2017.09.12
D.C.C.