Instructions / Assembly

WIRING
Without photocell
With photocell
CLEANING & MAINTENANCE:
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while
Fixture is energized.
1. Clean glass lens with non-abrasive glass cleaning solution.
2. Do not open fixture to clean the LED. Do not touch the LED
TROUBLESHOOTING
1. Check that the line voltage at fixture is correct. Refer to wiring directions.
2.Is the fixture grounded properly?
Note: These instructions do not cover all details or variations in equipment nor do they provide for
every possible situation during installation, operation or maintenance.
Universal voltage driver permits operation at 100V
to 277VAC, 50 or 60Hz except fixtures factory
ordered with a 120V photocell (/PC).
1. Connect the black fixture line to the (L) Live line
supply wire.
2. Connect the white fixture line to the (N) Neutral
line supply wire.
3. Connect the green fixture line to the (G) Ground
line supply ground.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru
277V, 50 or 60 Hz. For 0-10V Dimming, follow the wiring
directions as in fig. 4.
1. Connect the black fixture lead to the (+) LINE supply
lead.
2. Connect the white fixture lead to the (-) COMMON
supply lead.
3. Connect the GROUND wire from fixture to supply
ground. Do NOT connect the GROUND of the dimming
fixture to the output.
4. Connect the purple fixture lead to the (V+) DIM lead.
5. Connect the gray fixture lead to the (V-) DIM lead.
6. Cap the yellow fixture lead, if present. Do NOT
t