User's Manual

Table Of Contents
85
13
FAQ
Q1. How many types of communication ports does the Logger4000 support, what are
the corresponding ports, and how to set the port parameters?
TTyyppee
PPoorrtt
PPaarraammeetteerr sseettttiinngg
Ethernet
FE1~FE4
Default IP: 12.12.12.12; subnet mask: 255.255.255.0
Gateway: 12.12.12.1
DNS1: 1.2.4.8
DNS2: 8.8.8.8
RS485 A1B1~A7B7
Default Baud rate: 9600
Check bit: Null
Data bit: 8
Stop bit: 1
PLC
L1,L2,L3
Default Baud rate: 115200
Check bit: Null
Data bit: 8
Stop bit: 1
Q2. What are the forwarding protocols supported by the Logger4000?
PPrroottooccooll
DDeessccrriippttiioonn
ModbusRTU/ModbusTCP
The Logger4000 sends the collected data of devices (-
such as inverter, combiner box, Meteo Station) to the
background. The background allocates forwarding
addresses to theses devices, thereby accessing and
obtaining the data of the devices.
IEC104
1. Add or search devices on the Web interface (such
as inverter, combiner box, Meteo Station).
2. Export the IEC104 point table by clicking "Settings"
-> "IEC104 service settings". The point table shows
measuring point information of devices.