User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
80
12
Troubleshooting
12.1 Safety Instructions
The ground cable must be grounded reliably. Otherwise, electric shock may
occur to the operators!
12.2 Common Faults and Corrective Measures
The following table shows common faults and corresponding corrective measures. If
the fault still persists after you perform the corrective measures as described in this
manual, contact SUNGROW with the following information provided:
• Serial number of the Logger4000, date of manufacture, and software version
• Manufacture, type, configuration, and other information of device connected to the
Logger4000
• Fault information and brief description
• Picture of the fault (if possible)
FFaauulltt
PPoossssiibbllee ccaauussee
CCoorrrreeccttiivvee mmeeaassuurree
Failure to log into
the Web
1. Cable connection between
the PC and the Logger4000 is
abnormal.
1. Check whether the PC is
normally connected to the
port ETH of the Logger4000.
2. PC network signal is
abnormal.
2. Check whether the network
signal icon of the PC is
abnormal, like this
.
3. IP address of the PC is
incorrect.
3. Manually configure the IP
address of the PC network
port so that it is on the same
network segment as the IP
address of the Logger4000.