User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
79
11.2 Maintenance List
IItteemm MMeetthhoodd
Working
environment
Check to make sure there is no strong EMC interference device
around the Logger4000
Check to make sure there is no hot source around the Logger4000.
Check to make sure there is no corrosive materials around the
Logger4000
Hardware
maintenance
Check to make sure the power supply voltage is normal
Check to make sure the cables are connected firmly
Check to make sure the grounding cable is grounded properly
System
cleaning
Clean the enclosure, circuit board and the components
Check the heat dissipation hole and the ensure it is not covered
Terminal and
cable
connection
Check if the screws of the control terminals are loose. Refasten
them with screwdriver if necessary
Check if the connection copper bar or screws are discoloring
Visually check the wiring layout and the device terminal connection
Software
maintenance
Log in Web to check the device communication situation
Log in Web to check the parameter setting of the Logger4000
Log in Web to check the software version of the Logger4000
User Manual 11 Maintenance