User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
77
SSuubbsseeqquueenntt OOppeerraattiioonn
Delete digital input manner: select a digital input manner that needs to be deleted, and
click "Clear data".
10.2.2.6 Country Mode
If the dispatching input must be the national power dispatching instruction, the active
control mode is set to "Country mode".
step 1 Click "Power control" -> "Reactive power" to enter the reactive power interface.
step 2 Set the reactive control mode to "Country mode".
step 3 Select a country, PPC type, and instruction type, and click "Save".
-- -- EEnndd
10.2.2.7 Scheduling Prohibited
Set the reactive control mode to "Scheduling prohibited" if the Logger4000 is prohibited
to perform reactive dispatching on the inverter.
step 1 Click "Power control" -> "Reactive power" to enter the reactive power interface.
step 2 Set the reactive control mode to "Scheduling prohibited" and click “Save”.
-- -- EEnndd
10.2.3 Emergency Button
In inverters need to be stopped in batch, select the button "Emergency button".
Click "Power control" -> "Emergency button" to enter the corresponding interface.
PPaarraammeetteerr
DDeessccrriippttiioonn
Emergency button
Enable: The emergency button is turned on, and inverters are
stopped in batch.
Disable: The emergency button is turned off, and inverters are
restored to the boot in batch.
DI port
Associated with DI5 channel
User Manual 10 Grid Dispatching