User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
73
PPaarraammeetteerr
DDeessccrriippttiioonn
Error limit (%)**
Adjustment accuracy If the ratio of the difference between
the reactive power and the target value to the rated power
is within the set error range, the target value is reached.
Adjustment ratio (%)**
If the adjustment does not reach the set target value,
increase or decrease adjustment value according to the
set adjustment ratio, so as to reach the target value.
Reactive power
direction**
Forward: The reactive power direction of the inverter array
displayed by the meter/transformer is the same as the
actual reactive power direction.
Backward: The reactive power direction of the inverter
array displayed by the meter/transformer is opposite to
the actual reactive power direction.
Control cycle**
Time interval of delivering dispatching instructions.
Parameter range: 5~60s
Note:
The parameters noted with * refer to the parameters that need to be set only when the
Control Method is set to “Open-loop Control”.
The parameters noted with ** refer to the parameters that need to be set only when the
Control Method is set to “Closed-loop Control” .
step 4 After finishing parameter setting, click "Save" to save the operation.
-- -- EEnndd
10.2.2.3 Local Power Control
If reactive dispatching instruction or dispatching target value is used as dispatching
input locally, the reactive control mode is set to "Local power control".
step 1 Click "Power control" -> "Reactive power" to enter the reactive power interface.
step 2 Set the "Reactive control mode" to "Local power control".
step 3 Set local dispatching parameters. For specific parameter description, refer to the
following table.
User Manual 10 Grid Dispatching