User's Manual
Table Of Contents
- 1 About this Manual
 - 2 Safety Instructions
 - 3 Product Introduction
 - 4 Installation Flow
 - 5 Unpacking and Storage
 - 6 Mechanical Installation
 - 7 Electrical Connection
- 7.1 Safety Instructions
 - 7.2 Port Introduction
 - 7.3 Overview
 - 7.4 Connecting to the Inverter
 - 7.5 Connecting to the Meteo Station
 - 7.6 Connecting to the Energy Meter
 - 7.7 Wiring of DI Signal
 - 7.8 Wiring of DO Signal
 - 7.9 Wiring of AI Signal
 - 7.10 Wiring of PT Signal
 - 7.11 Connecting to the Remote Monitoring Device
 - 7.12 Connecting to the AC Power Supply
 - 7.13 Connecting to the DC Power Supply
 - 7.14 Earthing Connection
 
 - 8 Commissioning
 - 9 Web Interface
- 9.1 Running Requirements
 - 9.2 Login Steps
 - 9.3 Web Main Interface
 - 9.4 Operation Procedure
 - 9.5 Overview
 - 9.6 Device Monitoring
 - 9.7 Device Maintenance
 - 9.8 History Data
 - 9.9 System
- 9.9.1 Running Information
 - 9.9.2 System upgrade
 - 9.9.3 Log export
 - 9.9.4 Rebooting
 - 9.9.5 Reset all setting
 - 9.9.6 Remote Maintenance
 - 9.9.7 Message Export
 - 9.9.8 System Time
 - 9.9.9 Forwarding Configuration
 - 9.9.10 IEC104
 - 9.9.11 MODBUS
 - 9.9.12 Third-party portal
 - 9.9.13 Forward GOOSE Service Configuration
 - 9.9.14 Interface
 - 9.9.15 MPLC
 - 9.9.16 More
 - 9.9.17 About
 
 
 - 10 Grid Dispatching
 - 11 Maintenance
 - 12 Troubleshooting
 - 13 FAQ
 - 14 Appendix A: Technical Data
 - 15 Appendix B: Related Drawings
 - 16 Appendix C: General Information
 
70
PPaarraammeetteerr
DDeessccrriippttiioonn
Q-Method
kW: set active power value.
%: set active power percentage.
Select energy meter/
transformer*
Unselected
Select energy meter/transformer involved in power
regulation
Note: *Only when the control method is set to "Closed-loop control", the parameter "-
Select energy meter" is settable.
step 4 Add digital input manner.
Select the desired DI channel, fill in the "Percentage"(fixed value of active power), and
click "Save".
-- -- EEnndd
SSuubbsseeqquueenntt OOppeerraattiioonn
Delete digital input manner: select a digital input manner that needs to be deleted, and
click "Clear data".
10.2.1.6 Country Mode
If the dispatching input must be the national power dispatching instruction, the active
control mode is set to "Country mode".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Country mode".
step 3 Select a country and PPC type, and click "Save".
When the country is set to "Korea", corresponding parameter description is as follows:
table 10-5 Parameter description
PPaarraammeetteerr DDeessccrriippttiioonn
PPC type PPC device of DER-AVM type
Forwarding Modbus
ID
From 1 to 10
When the country is set to "Japan", corresponding parameter description is as follows:
10 Grid Dispatching User Manual