User's Manual
Table Of Contents
- 1 About this Manual
 - 2 Safety Instructions
 - 3 Product Introduction
 - 4 Installation Flow
 - 5 Unpacking and Storage
 - 6 Mechanical Installation
 - 7 Electrical Connection
- 7.1 Safety Instructions
 - 7.2 Port Introduction
 - 7.3 Overview
 - 7.4 Connecting to the Inverter
 - 7.5 Connecting to the Meteo Station
 - 7.6 Connecting to the Energy Meter
 - 7.7 Wiring of DI Signal
 - 7.8 Wiring of DO Signal
 - 7.9 Wiring of AI Signal
 - 7.10 Wiring of PT Signal
 - 7.11 Connecting to the Remote Monitoring Device
 - 7.12 Connecting to the AC Power Supply
 - 7.13 Connecting to the DC Power Supply
 - 7.14 Earthing Connection
 
 - 8 Commissioning
 - 9 Web Interface
- 9.1 Running Requirements
 - 9.2 Login Steps
 - 9.3 Web Main Interface
 - 9.4 Operation Procedure
 - 9.5 Overview
 - 9.6 Device Monitoring
 - 9.7 Device Maintenance
 - 9.8 History Data
 - 9.9 System
- 9.9.1 Running Information
 - 9.9.2 System upgrade
 - 9.9.3 Log export
 - 9.9.4 Rebooting
 - 9.9.5 Reset all setting
 - 9.9.6 Remote Maintenance
 - 9.9.7 Message Export
 - 9.9.8 System Time
 - 9.9.9 Forwarding Configuration
 - 9.9.10 IEC104
 - 9.9.11 MODBUS
 - 9.9.12 Third-party portal
 - 9.9.13 Forward GOOSE Service Configuration
 - 9.9.14 Interface
 - 9.9.15 MPLC
 - 9.9.16 More
 - 9.9.17 About
 
 
 - 10 Grid Dispatching
 - 11 Maintenance
 - 12 Troubleshooting
 - 13 FAQ
 - 14 Appendix A: Technical Data
 - 15 Appendix B: Related Drawings
 - 16 Appendix C: General Information
 
68
10.2.1.4 AI Control
When using the analog signal at the AI port of the Logger4000 as the dispatching input,
set the active control mode to "Analog input".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Analog input".
step 3 Set AI control parameters. For specific parameter description, refer to the following
table.
table 10-3 Parameter description
PPaarraammeetteerr
DDeessccrriippttiioonn
Control method
Open loop control: Active instruction controlled by AI is sent
to the power output port of the inverter, thereby achieving
active power control.
Closed-loop control:
• In case no Smart Energy Meter is selected, active
instruction controlled by AI is used as target value, and
active power compensation ratio is calculated and sent
to the power output port of the inverter. Generally, this
strategy is used for fast and accurate active power
regulation.
• In case a Smart Energy Meter is selected, active
instruction controlled by AI is used as target value,
active power of the meter needs to be collected and
used as input parameter, and active power
compensation ratio is calculated and sent to the power
output port of the inverter. Generally, this strategy is
used for anti-backflow or avoiding zero power feed-in.
Select energy meter*
Unselected
Select Smart Energy Meter involved in power regulation
Control cycle
Time interval of delivering dispatching instructions
Parameter range: 5~60s
AI port
AI1~AI4 available
Q-Method
kW: set active power value
%: set active power percentage
Min. Lower limit: 0.0
Max.
When "Q-Method" is set to "%", the upper limit is 100.0%
When "Q-Method" is set to "kW", the upper limit is 999999
kW
Step
The minimum difference value between two consecutive
power dispatching instructions
10 Grid Dispatching User Manual