User's Manual
Table Of Contents
- 1 About this Manual
 - 2 Safety Instructions
 - 3 Product Introduction
 - 4 Installation Flow
 - 5 Unpacking and Storage
 - 6 Mechanical Installation
 - 7 Electrical Connection
- 7.1 Safety Instructions
 - 7.2 Port Introduction
 - 7.3 Overview
 - 7.4 Connecting to the Inverter
 - 7.5 Connecting to the Meteo Station
 - 7.6 Connecting to the Energy Meter
 - 7.7 Wiring of DI Signal
 - 7.8 Wiring of DO Signal
 - 7.9 Wiring of AI Signal
 - 7.10 Wiring of PT Signal
 - 7.11 Connecting to the Remote Monitoring Device
 - 7.12 Connecting to the AC Power Supply
 - 7.13 Connecting to the DC Power Supply
 - 7.14 Earthing Connection
 
 - 8 Commissioning
 - 9 Web Interface
- 9.1 Running Requirements
 - 9.2 Login Steps
 - 9.3 Web Main Interface
 - 9.4 Operation Procedure
 - 9.5 Overview
 - 9.6 Device Monitoring
 - 9.7 Device Maintenance
 - 9.8 History Data
 - 9.9 System
- 9.9.1 Running Information
 - 9.9.2 System upgrade
 - 9.9.3 Log export
 - 9.9.4 Rebooting
 - 9.9.5 Reset all setting
 - 9.9.6 Remote Maintenance
 - 9.9.7 Message Export
 - 9.9.8 System Time
 - 9.9.9 Forwarding Configuration
 - 9.9.10 IEC104
 - 9.9.11 MODBUS
 - 9.9.12 Third-party portal
 - 9.9.13 Forward GOOSE Service Configuration
 - 9.9.14 Interface
 - 9.9.15 MPLC
 - 9.9.16 More
 - 9.9.17 About
 
 
 - 10 Grid Dispatching
 - 11 Maintenance
 - 12 Troubleshooting
 - 13 FAQ
 - 14 Appendix A: Technical Data
 - 15 Appendix B: Related Drawings
 - 16 Appendix C: General Information
 
66
PPaarraammeetteerr
DDeessccrriippttiioonn
Adjustment ratio (%)**
If the adjustment does not reach the set target
value, increase or decrease adjustment value
according to the set adjustment ratio, so as to
reach the target value.
Control Cycle**
Time interval of delivering dispatching instructions
Parameter range: 5~60s
The parameters noted with * refer to the parameters that need to be set only when the
Control Method is set to “Open-loop Control”.
The parameters noted with ** refer to the parameters that need to be set only when the
Control Method is set to “Closed-loop Control”.
step 4 After finishing parameter setting, click "Save" to save the operation.
-- -- EEnndd
10.2.1.3 Local Power Control
If active dispatching instruction or dispatching target value is used as dispatching input
locally, the active control mode is set to "Local power control".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Local power control".
step 3 Set local dispatching parameters. For specific parameter description, refer to the
following
10 Grid Dispatching User Manual