User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
64
10
Grid Dispatching
10.1 Function Description
Logger4000 is equipped with a power control module. The module is used to receive
control instructions from the grid dispatch center and send the control instructions to the
monitored inverter through the RS485 port, thereby controlling the active power,
reactive power, power factor, start/stop of the inverter.
10.2 Power Regulation
Power regulation includes active power control and reactive power regulation.
10.2.1 Active Power
10.2.1.1 Disable
If the inverter needs to operate at full load, the active control mode should be set to
"Disable".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Disable" and click “Save”.
-- -- EEnndd
10.2.1.2 Remote Power Control
When the instruction source is IEC104 or MODBUS TCP protocol, set the active control
mode to "Remote power control".
step 1 Click “Power control” -> “Active power” to enter the active power interface.
step 2 Set the active control mode to "Remote Power Control".
step 3 Set remote dispatching parameters. For specific parameter description, refer to the
following table.