User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
60
9.9.11.2 Client Mode
In the client mode, Logger4000 is used a Client and connected to PC server through
Modbus TCP protocol to implement data transmission and instruction delivery.
step 1 Click "System" -> "Transfer Configuration" -> "MODBUS" to enter the "Server" tab by
default.
step 2 Click "Client" to enter the corresponding tab.
step 3 Click "Add" to enter the "Advanced Settings" interface.
step 4 Enter the port number of the server and the peer port and click "Save".
-- -- EEnndd
9.9.11.3 RTU Mode
In the RTU mode, Logger4000 is connected to PC server through Modbus RTU protocol
to implement data transmission and instruction delivery.
step 1 Click "System" -> "Transfer Configuration" -> "MODBUS" to enter the "Server" tab by
default.
step 2 Click "RTU" to enter the corresponding tab.
step 3 Select serial port and enter delay time.
step 4 Click
.
-- -- EEnndd
9.9.12 Third-party portal
Configure the third-party cloud forwarding service for the Logger4000 on this interface.
step 1 Click "System" -> "Transfer configuration" -> "Third-party portal" to enter the
corresponding interface.
step 2 Turn on the switch.
step 3 Click the button
on the operation bar, so that an advanced setting window will pop
up.
step 4 Modify the configuration information and click "Save".
Set the FTP path and name it as "/FTP server directory".
For example, for the name "/SUNGROW", / is the root directory, and
SUNGROW is the directory where data is stored on the FTP server.
-- -- EEnndd