9.9.10.2 Export IEC104 Forwarding Point Table
step 1 Click "System"->"Transfer Configuration"->"IEC104" to enter the "Server" interface by
default.
step 2 Click
to export the forwarding point table in .xml or .csv format to local.
-- -- EEnndd
9.9.10.3 Client Mode
In the client mode, Logger4000 is used as a Client and connected to PC server to
implement data transmission and instruction delivery.
step 1 Click "System" -> "Transfer Configuration" -> "IEC104" to enter the "Server" tab by
default.
step 2 Click "Client" to enter the corresponding tab.
-- -- EEnndd
9.9.10.4 Add Peer Port Information
step 1 In Client mode, edit the IEC forwarding point table referring to " Edit IEC104 Forwarding
Point Table".
step 2 Click "Add" to enter the "Advanced Settings" interface.
step 3 Enter the port number of the server and the peer port, and select the remote signaling
measuring point type, remote signaling time mark, and upload with a change mode.
step 4 Click configuration
to import .xml file.
step 5 Click "Save".
-- -- EEnndd
9.9.11 MODBUS
Configure the MODBUforwarding service for the Logger4000 on this interface.
9.9.11.1 Sever Mode
In Sever mode, Logger4000 functions as a sever. Through Modbus TCP protocol, the
host computer server is connected to Logger4000 for data and instruction transmission.
step 1 Click "System"->"Transfer Configuration"->"MODBUS" to enter the "Sever" interface by
default.
step 2 Set white list referring to "9.9.10 IEC104".
-- -- EEnndd