User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
58
Click "System" -> "Transfer configuration" -> "IEC104" to enter the corresponding
interface.
SSeerrvveerr MMooddee
In the server mode, Logger4000 is used as a Server and connected to PC server to
implement data transmission and instruction delivery.
The local port is 2404.
WWhhiittee lliisstt sseettttiinngg
Click "White List Setting" to enter the interface.
When the option "Enable White List" is not selected, and the peer IP address is "0.0.0.0",
any background devices with valid IP address can access the Logger4000. When the
option "Enable White List" is selected, and peer IP address is entered, only the device
with the specified IP address can access the Logger4000.
GGeenneerraattee PPooiinntt TTaabbllee
Turn on the switch of local port 2404.
Click "Generate point table", and default IEC104 point table will be automatically
imported to configuration file.
EEddiitt IIEECC110044 FFoorrwwaarrddiinngg PPooiinntt TTaabbllee
step 1 Click “Export of Configuration Tools” to export configuration tools in .xsml format to
the local.
step 2 Decompress the exported package.
step 3 Click open the configuration tools in the decompressed folder and set the parameters in
the file. After setting, click "Export"->"IEC104 CFG" on the menu bar, and a pop-up
dialog box is displayed to indicate output completion. The IEC104 forwarding point table
in .xml format is generated.
The IEC104 forwarding point table and the configuration tools must be stored
in the same directory.
-- -- EEnndd
9.9.10.1 Import IEC104 forwarding point table
step 1 After editing the IEC104 forwarding point table, click
on the operation bar to enter
the "Advanced Settings" interface.
step 2 Click the button
on the pop-up window, to import the xml file.
step 3 Click "Save".
-- -- EEnndd