User's Manual
Table Of Contents
- 1 About this Manual
- 2 Safety Instructions
- 3 Product Introduction
- 4 Installation Flow
- 5 Unpacking and Storage
- 6 Mechanical Installation
- 7 Electrical Connection
- 7.1 Safety Instructions
- 7.2 Port Introduction
- 7.3 Overview
- 7.4 Connecting to the Inverter
- 7.5 Connecting to the Meteo Station
- 7.6 Connecting to the Energy Meter
- 7.7 Wiring of DI Signal
- 7.8 Wiring of DO Signal
- 7.9 Wiring of AI Signal
- 7.10 Wiring of PT Signal
- 7.11 Connecting to the Remote Monitoring Device
- 7.12 Connecting to the AC Power Supply
- 7.13 Connecting to the DC Power Supply
- 7.14 Earthing Connection
- 8 Commissioning
- 9 Web Interface
- 9.1 Running Requirements
- 9.2 Login Steps
- 9.3 Web Main Interface
- 9.4 Operation Procedure
- 9.5 Overview
- 9.6 Device Monitoring
- 9.7 Device Maintenance
- 9.8 History Data
- 9.9 System
- 9.9.1 Running Information
- 9.9.2 System upgrade
- 9.9.3 Log export
- 9.9.4 Rebooting
- 9.9.5 Reset all setting
- 9.9.6 Remote Maintenance
- 9.9.7 Message Export
- 9.9.8 System Time
- 9.9.9 Forwarding Configuration
- 9.9.10 IEC104
- 9.9.11 MODBUS
- 9.9.12 Third-party portal
- 9.9.13 Forward GOOSE Service Configuration
- 9.9.14 Interface
- 9.9.15 MPLC
- 9.9.16 More
- 9.9.17 About
- 10 Grid Dispatching
- 11 Maintenance
- 12 Troubleshooting
- 13 FAQ
- 14 Appendix A: Technical Data
- 15 Appendix B: Related Drawings
- 16 Appendix C: General Information
17
6 Mechanical Installation
6.1 Location Selection
This section is intended to guide the user in selecting an appropriate installation location.
IInnssttaallllaattiioonn LLooccaattiioonn RReeqquuiirreemmeennttss
• With the ingress of protection IP 20, the Logger4000 can be installed only indoors.
• Ambient temperature range: -30℃ to +60℃. The relative humidity should not exceed
95%. If otherwise, the internal components will be damaged.
• The installation environment should be free of inflammable, explosive, and corrosive
materials.
This equipment is not suitable for use in locations where children are likely to
be present
RReeqquuiirreemmeenntt ffoorr IInnssttaallllaattiioonn CClleeaarraannccee
Reserve enough clearances around the Logger4000.
Before installation, make sure the wiring terminals are at the bottom of the Logger4000
to prevent the dust or particles in the air penetrating into the device, impairing the
service life.
The installation location should be 1,500mm above the ground surface. Clearances of at
least 500mm should be reserved around the Logger4000 for ease of maintenance. The
follow figure shows the requirement for minimum clearances.
When there are external devices (such as Meteo Station) connected to the
Logger4000, users should install corresponding communication SPD according
to onsite conditions.