Instruction Manual

LED EMERGENCY PACK • SPLIT TYPE/L
INSTALL INSTRUCTIONS
Specifications subject to change without notice. Photos and line
drawings may not be to scale and are for general reference only.
TYPICAL WIRING DIAGRAM
EMERGENCY SYSTEM
N
WHITE
L BLACK
120-277V
WHT/BLK
Case must be grounded
DRIVER- (Black)
DRIVER+ (Red)
LED DRIVER
Blk-
Red+White
Black
Wall
Switch
PROGRAMMABLE OUTPUT
Constant Current Setting
• Preset by factory, or field adjustable
Adjustable Output Current
• 10 ranges at 100mA
• Plus 50mA fine tuning
10
5
8 2
7 3
9
1
6
4
0
5
x100 x10
Test+ (Purple)
Test Switch
BATTERY
LED+ (Grey)
LED- (White)
Note: For best performance, adjust dials to match output current provided by the fixture’s driver (see fixture driver label).
Caution: Do not adjust dials to exceed current provided by fixture’s main driver, or you may damage the LEDs and void warranty.
Example:
If the fixture driver label says output is 950mA, turn the X100 dial to “9” and the x10 dial to “5”.
If the fixture driver label says output is 600mA, turn the X100 dial to “6” and the x10 dial to “0”.
Test- (Brown)