Installing the Electrical Supply
This chapter provides information about electrical supply installation.
Note All supply connections, wiring, wire protection, and wire routing must be
made in accordance with applicable sections and requirements of national electrical
code and local electrical authorities.
System Switch
Caution The system switch does not isolate the equipment.
The system switch of the Netra t 1400/1405 system functions as a standby device
enabling and disabling the power module outputs. The system switch is a rocker,
momentary switch.
The system does not contain any integral circuit breakers. The system can be isolated
from the power only by using external circuit breakers.
All connections must be broken to isolate the system. To isolate the system, open all
external circuit breakers.
Note The ON/STBY switch handles low voltage signals only; the high-power
circuits do not pass through this switch.