Operation Manual
10 Netra t 1400/1405 Installation and User’s Guide • September 1999
FIGURE 2-4 Flange Mount Assembly
The chassis must be secured within the rack frame using screws suitable for the
equipment frame. They must be a minimum size of M5 (10/32) depending on the
frame requirement. All screws must be fitted; there are positions provided for a total
of 16 screws (four per flange). The recommended tightening torque value for M5
recess head screws is 4.0Nm (3.0lbf-ft).
Caution – For flange mounted installations, always fit four flanges.