Operation Manual

5
CHAPTER
2
Installing the System
Before you install the system, confirm that the correct power supply is available.
Refer to Chapter 3, "Installing the Electrical Supply", for further information.
Environmental Considerations
The system can be installed in an environment with the following specific parameter
ranges:
Ambient temperature
operating: to 40˚C
exceptional operating limit: –5˚ to 55˚C
1
,
2
storage: –40˚ to 70˚C
Relative humidity
operating: 5 to 85% non-condensing
3
storage: 10 to 95% non-condensing
Elevation
operating: –300 to +3000 meters
storage: –300 to +12000 meters
Dimensions
Height: 264mm (10.39in.) 6U nominal
Width: 431.8mm (17.00in.)
Depth: 477.3mm (18.79in.)
Weight (unpackaged): maximum 32kg (71lb)
1. Error-freeoperationofthe removable media devicesisfrom0° to40°C.
2. Nomorethan96 hoursdurationat extremesand at elevationslessthan 1800m.
3. Subjectto a maximumabsolutehumidity of0.024kgof water perkgof dryair.
LW3User.book Page 5 Wednesday, November 10, 1999 9:00 AM