Figure 5-8. Series/Parallel Connection for 4-Terminal Batteries (Low or High Rate Applications) 
5.3 Discharging 
Discharge data for Sun Xtender®  AGM  batteries are given in Appendix C. The capacity 
delivered by the battery depends on the rate of discharge as well as the battery temperature. 
The battery will deliver less capacity as the discharge rate increases and less capacity as the 
temperature is lowered. Graphs are provided in Appendix C to quantify these effects. Peukert 
plots (Amps vs Time) are also included, along with formulas for calculating the current that can 
be removed or any discharge time from 0.5 hours to 120 hours. To calculate the discharge time 
for a specified amperage, these formulas can be inverted as follows: 
A = C x T 
-n
T = C
1/n 
 x A
-1/n
(A = Amps, T = Time in hours, C & n are constants specific for each battery model) 
In general, batteries should be sized such that the rated capacity is at least twice the capacity 
required by the load.  For example, if 100 Ah is required on average, select at least a 200Ah 
battery. This approach will limit the average depth of discharge to 50% and will dramatically 
extend the life of the battery (see chart of Cycle Life versus Depth of Discharge in Appendix C). 