SunXtender Technical Manual
Table Of Contents
Document No. 6-0100 Rev. H   
Page 35 of 43 
APPENDIX C – CHARTS AND GRAPHS 
Battery Load Voltage vs. DOD 
Below are listed the 1 hour, 8 hour, 24 hour and 120 hour load voltages during a discharge 
cycle to 100% discharge (10.5V endpoint) for a 12V battery at 25°C (77°F). 
DOD (%) 
1 hr. Rate 
8 hr. Rate 
24 hr. Rate 
120 hr. Rate 
10 
12.23 
12.60 
12.65 
12.69 
20 
12.16 
12.51 
12.55 
12.58 
30 
12.07 
12.39 
12.42 
12.45 
40 
11.96 
12.25 
12.28 
12.32 
50 
11.83 
12.11 
12.15 
12.18 
60 
11.70 
11.98 
12.02 
12.05 
70 
11.55 
11.79 
11.83 
11.88 
80 
11.38 
11.59 
11.61 
11.65 
90 
11.15 
11.32 
11.34 
11.40 
100 
10.50 
10.50 
10.50 
10.50 
  NOTE: Multiply by 2X for a 24V battery bank and by 4X for a 48V battery bank 
Note that these voltages are approximate and will vary as the battery ages. They are, however, 
a  fair  indicator of state of charge and can be used when setting low voltage alarms or 
disconnects. For example, if the average load is 50A and the battery has a rated capacity of 400 
AH at the 8-hour rate, the minimum discharge voltage would be 12.11 volts for a 50% DOD.  
SOC (%) vs. OCV 
An easy method to estimate the State of Charge (SOC) of the battery is by measuring its Open 
Circuit Voltage (OCV). This measurement should be made after the battery has been at rest for 
a minimum of four hours with the battery shut off  from its charging source and load. The 
reference temperature is 25°C (77°F), but the OCV does not change appreciably at other 
temperatures (temperature coefficient is 0.18 millivolts/cell per °C). 
State of 
Charge (%) 
OCV of 
2V battery 
OCV of 
6V battery 
OCV of 
12V battery 
OCV of 
24V battery 
OCV of 
48V battery 
100 
>2.13 
>6.39 
>12.78 
>25.56 
>51.12 
90 
2.11 
6.33 
12.66 
25.32 
50.64 
80 
2.09 
6.27 
12.54 
25.08 
50.16 
75 
2.08 
6.24 
12.48 
24.96 
49.92 
70 
2.07 
6.21 
12.42 
24.84 
49.68 
60 
2.05 
6.15 
12.30 
24.60 
49.20 
50 
2.03 
6.09 
12.18 
24.36 
48.72 
40 
2.01 
6.03 
12.06 
24.12 
48.24 
30 
1.99 
5.97 
11.94 
23.88 
47.76 
25 
1.98 
5.94 
11.9 
23.76 
47.52 
20 
1.97 
5.91 
11.82 
23.64 
47.28 
10 
1.95 
5.85 
11.70 
23.40 
46.80 
0 
<1.93 
<5.79 
<11.58 
<23.16 
<46.32 
These voltage levels are applicable for aged batteries. The voltage levels for a new battery will 
be somewhat higher at a given state of charge. For example, a new battery typically has an 
OCV of 2.17 volts per cell (13.0 for a 12V battery) or higher at 100% SOC.  