PARAMETER DEF. DESCRIPTION
Pump is automatically restarted if the readen
value goes below the maximum value for a period
of at least 5 seconds.
Min alarm value
XXX.X [bar]
0
Minimum value allowed in the system. If the
readen value goes lower than this value, an alarm
occurs and the pumps is stopped. Pump is
automatically restarted if the readen value goes
higher than the minimum value for a period of at
least 5 seconds.
PARAMETER DEF. DESCRIPTION
Freq. min. control
XXX [Hz]
80
Minimum frequency below which the pump tries
to stop
Stop delay
XX [s]
60
Delay for which the pump tries to stop below
freq. min. control.
MPPT: volt. gap
dV = XX.X [V]
XX
MPPT voltage gap
MPPT: time gap
dVt= XX.X [s]
XX
MPPT time gap
MPPT: freq. gap
df= XX.X [Hz]
XX
MPPT frequency gap
Ki
XX
50
Kp and Ki parameters allow the dynamic control
of the system. Set values (Ki=50, Kp=005) are
usually enough to get a valid dynamic control.
Kp
XX
5
Kp and Ki parameters allow the dynamic control
of the system. Set values (Ki=50, Kp=005) are
usually enough to get a valid dynamic control.
Dry run thresh.
DR_thr = X.XX
0.5
Threshold of water level sensor.
Restarts delay
XX [min]
1
Restart delay after a dry running alarm. At each
tentative (max 5) restart delay will be doubled.
Digital input 1
N.O./N.C.
N.O.
By selecting N.A. (normally open) CM MP runs
the pump if the digital input 1 is open; pump will
be stopped if the digital input 1 is closed.
By selecting N.C. (normally closed) CM MO runs
the pump if the digital input 1 is closed; pump
will be stopped if the digital input 1 is opened.