4.2 Installer Parameters
Pressing ENTER where you are in (Menu/ ENT to access), the following MENU is displayed:
MENU
Instal. Param.
Password required to enter (default 001)
To exit the Menu level and return to INITIAL DISPLAY is enough to press STOP button.
PARAMETER DEF. DESCRIPTION
Control Mode:
MPPT
Constant Value
Fix Speed
Constant Value 2 Set
Fix Speed 2 Val.
External Speed
MPPT
Mode of Control:
MPPT: pump speed is adjusted in order to
obtain maximum power available from PV
panels
Constant Value: Pump changes its speed to
keep the set value constant regardless of
water demand
Fix Speed: the pump runs at set frequency
Const. value 2 set: the two values are
selected by opening or closing the digital
input IN2
Fix speed 2 val: the two values are selected
by opening or closing the digital input IN2
External speed: control pump frequency by
using analog input AN4
Control mode: MPPT
Unit
XXXXX
bar
Unit
F. scale sensor
P = XX.X [bar]
16
Sensor full scale
Min value sensor
P = XX.X [bar[]
0
Sensor minimum value
Max alarm value
XXX.X [bar]
10
Maximum value allowed in the system. If the
readen value goes over this value, an alarm
occurs and the pump is stopped