Manual

Periodic autorun
T = XX [h]
0
Pump periodic autorun after XX hours of
inactivity. Value 0 makes function disabled.
Warning: review the advice in Chapter 1.
AN1, AN2 function
XXXXXX
Independent
Function logic for analog input AN1, AN2
(independent, lower value, higher value,
difference 1-2).
Offset input 1
[%]
20%
Zero correction for analog input 1 (4-20 mA)
(20 mA x 20% = 4 mA).
Offset input 2
[%]
20%
Zero correction for analog input 2 (4-20 mA)
(20 mA x 20% = 4 mA).
Offset input 3
[%]
0%
Zero correction for analog input 3 (0-10 mA)
(10V x 00% = 0 V).
Offset input 4
[%]
0%
Zero correction for analog input 4 (0-10 mA)
(10V x 00% = 0 V).
Language
XXXXXX
XXXX
End user communication language
5. Protections and alarms
Anytime a protection occurs a blinking message is displayed; on STATUS on INITIAL VIEW the
protection is displayed; by pressing STOP button (only and exclusively from the this position of
STATUS on INITIAL VIEW) is possible to try to reset the alarm; if CM MP does not reset the alarm it
is displayed again.
ALARM MESSAGE
ALARM DESCRIPTION
POSSIBLE SOLUTION
OVERCURRENT MOT.
Pump overload
Check possible causes about the
overload.
UNDER VOLTAGE
Supply voltage too low
Check possible causes of under voltage
OVER VOLTAGE
Supply voltage too high
Check possible causes of overvoltage
OVER TEMP. INV.
Inverter over
temperature
Make sure than ambient temperature is
less than 35 °C.
NO WATER
Pump is running dry.
Check water level.
Check that the level sensor is completely
immersed in water. CM MP tries to run
the pump after 5 minutes.
WARNING: if dry running protection
occurs, CM MP tries to start the pump
automatically.