Manual

Digital input 2
N.O./N.C.
N.O.
By selecting N.A. (normally open) CM MP runs
the pump if the digital input 2 is open; pump will
be stopped if the digital input 2 is closed.
By selecting N.C. (normally closed) CM MP runs
the pump if the digital input 2 is closed; pump
will be stopped if the digital input 2 is opened.
Digital input 3
N.O./N.C.
N.O.
By selecting N.A. (normally open) CM MP runs
the pump if the digital input 3 is open; pump will
be stopped if the digital input 3 is closed.
By selecting N.C. (normally closed) CM MO runs
the pump if the digital input 3 is closed; pump
will be stopped if the digital input 3 is opened.
Digital input 4
N.O./N.C.
N.O.
By selecting N.A. (normally open) CM MP runs
the pump if the digital input 4 is open; pump will
be stopped if the digital input 4 is closed.
By selecting N.C. (normally closed) CM MO runs
the pump if the digital input 4 is closed; pump
will be stopped if the digital input 4 is opened.
Dig.in.2/3 delay
T = XX [s]
3
Digital input IN2 and IN3 delay
Digital input IN1 and IN4 have 1 second fix delay
Change PASSWORD1
ENT
Pressing ENT allows the installer level password
(1
st
level) (default 001) to be changed
4.3 Advanced Parameters
Pressing ENTER where you are in [MENU’ / ENT to access], the following MENU is displayed:
MENU
Advanced param.
Password required to enter (default 002)
To exit the Menu level and return to INITIAL DISPLAY is enough to press STOP button.
PARAMETER DEF. DESCRIPTION
Max input Amp.
I = XX.X [A]
16
Max input current
Max Motor freq.
XXX [Hz]
XX
Maximum motor frequency. Note: by reducing
the maximum motor frequency, maximum
current will be reduced as well.
Autorestart
ON/OFF
OFF
If ON is selected, after a lack of voltage, the
pump returns to its normal status; if the pump
was running before the voltage drop, it resumes
to run automatically. Warning: review the advice
in Chapter 1.
10