Instruction Manual
14 
d7 
Defrost stop temperature 
0℃ ~ 50℃ 
12℃ 
℃/℉ 
32℉ ~122℉ 
d8 
Dripping time 
0~60 
0: Disabled 
2 
min 
d9 
Delay time for displaying the 
cabinet temperature after defrost 
0~90 
10 
min 
d10 
Defrost start delay 
0~60 
0: Disabled 
10 
min 
d11 
Defrost mode 
0: Electric defrost 
1: Hot gas defrost 
0 
/ 
F1 
Fan working mode 
0: Fan and compressor run or stop 
simultaneously; 
1: Fan runs continuously and stops 
during defrost; 
2: Fan runs continuously and stops 
during defrost and dripping; 
3: Fan runs continuously, stops during 
defrost and delays after defrost; 
4: Fan is controlled by defrost sensor 
temperature, and stops during defrost. 
3 
/ 
F2 
Fan start delay after the controller 
is energized 
0~60 
3 
min 
F3 
Fan delay time after defrost 
0~60 
0: Disabled 
2 
min 
A1 
Duty cycle mode in the event of a 
faulty cabinet sensor 
0: Disable 
1: Enable 
1 
/ 
A2 
Compressor off time in duty cycle 
mode 
1~60 
5 
min 
A3 
Compressor on time in duty cycle 
mode 
1~60 
30 
min 
A4 
Buzzer beep 
0: Disable 
1: Enable 
1 
/ 
A5 
Low alarm temperature(cabinet) 
-50℃ ~ High alarm temperature 
(cabinet) 
-10℃ 
℃/℉ 
-58℉ ~ High alarm temperature 
(cabinet) 
A6 
High alarm temperature(cabinet) 
Low alarm temperature(cabinet) ~ 85℃ 
24℃ 
℃/℉ 
Low alarm temperature(cabinet) ~ 185℉ 
A7 
Alarm delay 
0~60 
20 
3min 
A8 
Alarm delay after switch-on of the 
device 
0~60 
40 
3min 
A9 
High alarm offset 
1℃ ~30℃ 
10℃ 
℃/℉ 
1℉~ 60℉ 
A10 
Low alarm offset 
1℃ ~30℃ 
5℃ 
℃/℉ 
1℉~ 60℉  
A11 
Cabinet temperature alarm 
0: Absolute temperature point 
1: Temperature set-point + alarm offset 
0 
/ 