Instruction Manual
13 
PARAMETER TABLE 
Item 
Description 
Setting Range 
Default 
Unit 
User Menu 
St 
Temperature set-point 
Low set-point~High set-point 
4℃ 
℃/℉ 
Po 
Administrator menu password 
00~99(Default password is 55 and 
unchangeable) 
00 
/ 
Administrator Menu 
C1 
Differential 
0.5℃~9.0℃ 
4℃ 
℃/℉ 
1℉~20℉ 
C2 
Compressor start delay between 
last switch-off and the successive 
switch-on 
0~60 
5 
min 
C3 
Compressor start delay after 
switch-on of the device 
0~90 
5 
min 
C4 
Calibration temperature 1. 
Temperature value added to the 
value read by cabinet sensor 
-10.0℃~10.0℃ 
0.0℃ 
℃/℉ 
-20℉~20℉ 
C5 
Low set-point. Minimum possible 
set-point 
-50℃ ~Temperature set-point 
-2℃ 
℃/℉ 
-58℉ ~Temperature set-point 
C6 
High set-point. Maximum possible 
set-point 
Temperature set-point ~ -85℃ 
22℃ 
℃/℉ 
Temperature set-point ~ -185℉ 
C7 
Maximum standby time after 
compressor start delay① 
0~90 
0: Disabled 
9 
min 
C8 
Minimum compressor on time 
0~90 
0: Disabled 
0 
min 
d1 
Evaporator sensor options 
0: Disable 
1: Enable 
0 
/ 
d2 
Calibration temperature 2. The 
temperature value added to the 
value read by the evaporator 
sensor. 
-10.0℃~10.0℃ 
0.0℃ 
℃/℉ 
-20℉~20℉ 
d3 
Defrost counting type 
0: Compressor operating time 
1: Controller power-on time 
1 
/ 
d4 
Defrost interval time 
0~90 
0: Disable defrost 
2 
hour 
d5 
Display during defrost 
0: Displays cabinet temperature; 
1: Displays dEF during defrost and d9, 
displays cabinet temperature after d9 
elapses; 
2: Displays dEF during defrost and 
dripping; 
3. Displays cabinet temperature at 
defrost start during defrost and dripping. 
4. 
2 
/ 
d6 
Maximum defrost duration 
1~90 
25 
min 










