Installation Guide

869 STYLE D INITIATION MODULE
Installation Guide
DESCRIPTION
GND
FAU LT
A
GND
FAU LT
B
MODEL 869
A1
A1
A2
A2
B1
B1
B2
B2
LOOP
A
GND
AUX
LOOP
B
The 869 Style D Initiating Module
provides two supervised, power
limited Style D, 4-wire initiating
zones for connecting waterflow
switches and non-powered fire and
burglary devices to XR150/XR550
Series panels.
The module supervises both zones
for opens, shorts, or ground fault
conditions and requires 8.0VDC
to 25.0VDC auxiliary power, a
common ground, and one or two
alarm zone inputs from the panel.
Program the two alarm zone inputs
according to the types of devices
being used on the 869 module.
Compatibility
XR150/XR550 Series panels
What is Included?
One 869 Initiating Module
Hardware Pack
1
MOUNT THE MODULE
Themodule can be mounted in a DMP enclosure using the
standard3-hole mounting pattern. Refer to Figure 2 as needed
during installation.
1. Hold the plastic standos against the inside of the enclosure
side wall.
2. Insert the included Phillips head screws from the outside of
the enclosure into the standos. Tighten the screws.
3. Carefully snap the module onto the standos.
WIRE THE MODULE
2
Caution: Disconnect all power from the panel before wiring
the module. Failure to do so may result in equipment damage
or personal injury.
For power connections, use 22 AWG or larger wire. Refer to
Figure 3 when wiring the module.
1. Connect module Terminals A1 and A2 to zone A devices.
2. Connect module Terminal LOOP A to a panel zone 1-8.
3. Connect module Terminal GND to panel ground or battery
negative.
4. Connect module Terminal AUX to auxiliary power
(8.0VDC-25.0VDC).
5. Connect module Terminal LOOP B to a panel zone 1-8.
6. Connect module Terminals A1 and A2 to zone B devices.
Figure 1: 869 Module
Figure 2: Stando and Module Installation
BACK
1
2
3