Installation
12
Locating&CuttingRoof/CeilingOpenings
IMPORTANTNOTE:
Do not allow debris to fall into the furnace. This
couldcauseunsafeoperationandvoidthefurnace
warranty.Usethetopcapthatcomeswiththefurnace
packaging(oralternateprotector)topreventdebris
fromfallingintothefurnacebeforethenalroofjack
connection is made.
NOTE: Refer to the installation instructions provided
with optional air conditioning packages when installing
furnaces with optional cooling coil cabinet or with optional
C* series indoor coils.
1. Locate center of roof jack opening, measure 13 1/2”
from the rear wall of closet or alcove along the center
lineoffurnaceandooropening.SeeFigure 19.
2. Cut ceiling and roof holes:
•Ceiling=83/4”(222mm)diameter
•Roof=93/8”(238mm)diameter
InstallingTheRoofJack
1.Applycaulkingcompoundonundersideofroofashing
to form a continuous strip at least 3/8” wide around the
undersideoftheperimeteroftheashing.SeeFigure
20 or Figure 21 (page 13).
2. Connect roof jack assembly to the furnace. Insert
telescoping roof jack Assembly through the opening
cut on the roof.
3.Connectuepipetouecollaroffurnace.SeeFigure
22 (page 13).
4. Connect combustion air pipe to furnace collar with sheet
metal screw. See Figure 22.
NOTES:
• Itisrecommendedthattheconnectionofthecombustion
airpipetothefurnacebemadebeforetheashingis
secured to the roof to maintain alignment of roof jack
and furnace connections.
• Forreplacementfurnaces,besuretheinneruepipe
connects over the furnace vent collar. DO NOT use a
smallerdiameterinneruepipewhichcouldslide
insidethefurnaceventcollarandrestricttheow
offurnaceueproducts.
5.Attach roof ashing. If necessary, shift roof ashing
slightly in the roof opening so that assembly is in
alignment with furnace.
NOTE: If ashing is mountedon 12 degreeangle, it
may be necessary to adjust the angle to match the roof
pitch; (1/12 - 4/12 maximum).
6.Pressdownrmlyonroofashing(overcaulking)to
make the seal with roof water tight.
7.Secureashingwithappropriatefasteners. NOTE:For
addedprotectionagainstleaks,coattheashingplate
and fasteners with approved roofing compound.
Figure 18. Exampleof2½/12SlantJack
withFlashing
5/12 ROOF SLOPE
2
SLANT DECK
/12
1
2
ROOF JACK WITH
2
FLASHING
/12 SLANT
1
2
CEILING
CUT-OUT FOR
FLUE AND
ROOF JACK
C
L
C
L
24"
20"
13 1/2"
REAR WALL OF CLOSET OR ALCOVE
10"
FURNACE
OUTER
DOOR
FURNACE OUTLINE
Figure 19. Cut-OutDimensionsfor
Flue&RoofJack
Table 5
Table 5. SlantDeckFlashings
ROOFJACK
SERIES
IF ROOF
PITCHIS:
SLANTDECK
FLASHING
NUMBER
“X”
FACTOR
IS:
“F Series
2” in 12” 903893 (2.5/12) 2-1/8”
2-1/2” in 12” 903893 (2.5/12) 2-1/2”
3” in 12” 903894 (3/12) 2-7/8”
3-1/2” in 12” 903894 (3/12) 3-1/4”
4” in 12” 903895 (4/12) 3-5/8”
“S”Series
(2.5/12Pitchonly)
4-1/2” in 12” 903895 (2.5/12) 2-1/8”
5” in 12” 903895 (2.5/12) 2-1/2”
5-1/2” in 12” 903894 (3/12) 2-7/8”
6” in 12” 903894 (3/12) 3-1/4”
6-1/2” in 12” 903895 (4/12) 3-5/8”
Optionaldeckashingsforatand2.5/12pitchroofjacks.
4/12 pitch roof jacks not applicable.