- Studer Sinewave Inverter, Battery charger User and Installer Manual COMPACT C1312COMPACT C1312COMPACT C1312COMPACT C1312 COMPACT C2324COMPACT C2324COMPACT C2324COMPACT C2324 COMPACT C3548COMPACT C3548COMPACT C3548COMPACT C3548

STUDER INNOTEC
COMPACT
COMPACTCOMPACT
COMPACT
User manual COMPACT V2.0 E 23
8 Technical Data
Type
C1312
C1312C1312
C1312
C2324
C2324C2324
C2324
C3548
C3548C3548
C3548
Inverter
Nominal battery voltage 12V 24V 48V
Input voltage range 9.5 – 16V 19 – 32V 38 – 64V
Nominal power (W) 1300VA 2300VA 3500VA
Maximum power 30 min 1600VA 2500VA 4000VA
Maximum power 3min. 2000VA 3000VA 4800VA
Maximum power 5 sec 3500VA 6000VA 9000VA
Maximum load Up to short circuit
Asymmetrical load max. Up to Pnom
Standby adjustable 1 – 25W
Cos ϕ
0.1 – 1
Maximum efficiency 94% 95% 95%
Power OFF, Standby, ON 0.5W-0.6W 0.8W-09W 1.2W-1.4W
Power normal working no load 6W 9W 12W
Output voltage
230Vac ± 10%
Output frequency quartz controlled
50 Hz± 0.05 %
Maximum distortion < 2%
Dynamic behaviour 0 100 %
0.5ms
Overload and short circuit protection Automatic disconnection with 5 time restart attempt
Overheating temperature protection Acoustic warning before shut-off. Automatic restart
Battery Charger
Charging current adjustable 0-55A 0-55A 0-50A
Setting of AC INPUT current POWER SHARING 0 to 15A
Maximum input voltage 265 Vac , 350 V peak
Minimum input voltage Adjustable 150 – 230Vac
Frequency range 44 – 65Hz
Power factor correction (PFC) EN 61000-3-2 EN 61000-3-2
Solar Charge Regulator-Floating
Maximum no load voltage 25V 45V 90V
Maximum charging current 30A 30A 20A
Function principle Shunt regulator I / U / Uo / equalize
Battery Monitoring (25°C) in accordance with TLBM
(True Level Battery Management)
*Absorption charge time 0 – 4h
*End of charge cycle voltage 14.4V 28.8V 57.6V
*Floating voltage 13.6V 27.2V 54.4V
*Equalization voltage every 25 cycles 15.3V 31.6V 63.2V
*Low battery disconnection voltage 10.8V 21.6V 43.2V
Temperature compensation (Option) 3mV / °C / cell
Various data
Potential free Multifunction contact 16A - 250Vac / 3A – 60 dc
Weight 16.0kg 17.1kg 29.4kg
Dimension H * W * L (mm) 124 / 215 / 480 124 / 215 / 480 124 / 215 / 670
Protection index IP IP22
EEC – Compliance EN50081 I/II, EN 55014 – EN 55022, EN 61000-3-2
IEC 801 I/II/III/IV, CEI 555, IEC 1000-3-2, LVD 73/23/EEC
Operating temperature -20 to 55°C
Ventilation from 45°C
Commutation time (UPS-Mode) 20 ms
Noise level without/with ventilation (dB) < 10 / < 35 / 50dB
Options
Remote control (111.5 x 136.5 x 25mm / 20m Cable) RCC-01
Temperature sensor (58 x 51.5x 22mm / 3m Cable) CT-35
Protection cover for terminals CFC - 01
IP 23 Protection cover for COMPACT CIP - 23
We reserve the right to make any changes without issuing any prior notice
*These value can be modified according to the table chapter 5.3.1