STUDER INNOTEC COMPACT User and installer Manual Sinewave Inverter, Battery charger COMPACT C1312 COMPACT C2324 COMPACT C3548 Temperature sensor CT-35 Remote control RC-01 Solar charge regulator Cxxxx-S Remote power sharing RPS-01 AC cable cover CFC-01 IP-23 top cover CxxxxIP23 STUDER INNOTEC Rue des Casernes 57 CH-1950 SION User manual TEL: ++41 (0)27 205 60 80 FAX: ++41 (0)27 205 60 88 info@studer-inno.com COMPACT V2.
STUDER INNOTEC COMPACT Index table 1 GENERAL INFORMATION.................................................................................................................................... 4 1.1 1.2 1.3 1.4 1.5 1.6 2 OPERATING INSTRUCTIONS .................................................................................................................................... 4 QUALITY AND WARRANTY ...............................................................................................................
STUDER INNOTEC COMPACT 4.7.3 Delayed mode of the Transfer System......................................................................................................... 17 4.8 THE SOLAR CHARGE REGULATOR (OPTION) ......................................................................................................... 17 4.9 THE MULTIFUNCTIONAL CONTACT ...................................................................................................................... 17 4.10 THE REMOTE CONTROL...........
STUDER INNOTEC COMPACT 1 General Information 1.1 Operating instructions This manual is a part of the delivery package of every COMPACT inverter-charger. It serves as guidelines for safe and efficient operation of COMPACT.
STUDER INNOTEC COMPACT During operation of COMPACT, high tensions are generated at the connections and inside of the appliance which could be deadly fatal. Work on the appliance and on the installation should only be carried out by qualified and trained personnel. The whole installation connected with the COMPACT must comply with the respective valid codes and ordinances.
STUDER INNOTEC COMPACT 2 Introduction The COMPACT is a sine wave inverter with integrated battery charger and solar charger regulator with many additional functions, it has been developed to be used as stand-alone (independent of a grid-system) AC provider, or as continuous / break-free current supply provider. 2.
STUDER INNOTEC COMPACT 2.2.4 The solar charge regulator (optional) With the built-in solar charge regulator, the COMPACT is a complete solar-power-center. In a solar installation this regulator ensures that the batteries are charged correctly. With the COMPACT, batteries can be charged with a generator and with the solar modules at the same time. The charging of batteries with both energy sources is carried out fully automatically. 2.2.
STUDER INNOTEC 2.3.3 COMPACT Parallel- Series Connection: 12V 12V 12V 12V 24V 3 Assembly 3.1 Place of assembly The location of the COMPACT must be chosen by the following criteria: Protection from unauthorized handling. Dry dust free room, no condensation. Never install directly over the battery and never in a cabinet together with the batteries. Keep ventilation holes free.
STUDER INNOTEC COMPACT 3.3.2 Protection cover for the terminals connections The protection is available in option (Order ref. CFC-01) and avoid to do wrong hazardous connection on the terminals 230Vac. It mounted with strain relief clamps for the cable. 3.4 Connecting Plan / Front side M A N L Don't open before disconnect line and battery O Caution: Check battery polarity (+/-) before connecting! A wrong connection could damage the system. BATTERY Remote Power sharing . Remote control Temp.
STUDER INNOTEC K L AC Output Caution… M N O Don‘t … 15A Protection Remote Power Sharing COMPACT Connecting terminal for AC-output Caution: Check Polarity(+/-) before connecting the battery! Polarity reversal can damage the COMPACT. Do not open without disconnecting all terminals 15A Protection switch for the Transfer system Input current repartition 3.5 Cabling/wiring Connecting of the COMPACT is a very important step in the installation.
STUDER INNOTEC COMPACT 3.5.5 Connect the Solarmodules: SOLAR +/- (Only for solar option) Solar modules are connected on these terminals. Under no circumstances should any other energy source i.e. wind generator be connected to these terminals! Only solar modules must be connected with two cables +/-. Depending on the power of the modules, the cable cross section should be 2.5 up to 6mm2 .
STUDER INNOTEC COMPACT 4 Operating 4.1 Display and operating control elements POWER MONITOR Charge current Cha r g er - I n ver t er INPUT LIMIT CHARGER 16A 0 TRANSFER 0 AC IN 1 CHARGER 2 SOLAR CHARGE 3 22 20W 230V 70A 26 150V 23 [A] 70 60 50 40 30 20 10 STANDBY OFF 24 8 Inverter output power [%] 200 160 130 100 80 60 40 20 10 5 25 AC OUT 7 9 14 EQUALIZE Program 4 15 Contact active 5 16 Contact manual 6 AUX.
STUDER INNOTEC 4.2 Light Emitting Diodes: LED 1 Marking AC IN 2 CHARGER 3 SOLAR CHARGE Program Contact active Contact manual 4 5 6 7 8 AC OUT 9 10 INVERTER Over Temp. 11 Overload 12 13 Batt. Low/High OFF 14 15–18 25 4.3 19 20 21 4.4 22 23 24 26 COMPACT CURRENT MONITOR LED lit Voltage corresponding to selfadjusted values is at the AC IN input. Battery Charger is working Connected Solarmodules are delivering energy Program mode for Aux. Contact Auxiliary Contact is activated Aux. Cont.
STUDER INNOTEC 4.5 COMPACT The Inverter An Inverter is built in the COMPACT, which generates a sinusoidal alternating voltage of a very high quality. With this Inverter any alternating voltage consuming device 230Vac up to the nominal power of your COMPACT can be operated. Thanks to the generous dimensioning of the COMPACT, you can operate appliances requiring higher power than the nominal power of the COMPACT for a short time. The COMPACT provide up to 3-times the nominal power to start motors.
STUDER INNOTEC COMPACT 4.6 The Battery charger 4.6.1 Cycle of charge The full automatic COMPACT Battery Charger is adjusted at the factory so that most lead-acid and lead-gel batteries can be charged to the maximum. As soon as the minimum alternating voltage for the AC IN set on the Turning Knob 23 is available at the input (LED 1 AC IN is lit), the Battery Charger is switched on automatically (LED 2 CHARGER is lit).
STUDER INNOTEC COMPACT the OUTPUT less it’s give to the charger. Priority for the OUTPUT. When the power sharing is used the LED 200% (red) is lit to point out that’s the charge is limited. Caution: If the power use on the OUTPUT is higher than the value of the INPUT LIMIT (26) the COMPACT limit the current, then the generator means to stop or the circuit breaker before means to break. In option, a remote control (RPS-01, 20m cable) allows the Power Sharing far from the COMPACT. 4.6.3.
STUDER INNOTEC COMPACT Note: In the Inverter operation, The COMPACT generates a true sinusoidal and quartz stabilized output voltage. When, however the COMPACT is supplied from a grid or a generator and the transfer contact is active, then you have at the output AC OUT the same voltage as that at the input. This voltage can not be modified by the COMPACT! 4.7.1 Set the transfer voltage threshold The voltage threshold of the transfer can by adjust between 150 to 230V with the turning knobs (23).
STUDER INNOTEC COMPACT Maximum Contact load: -230Vac /16Amp-30Vdc/1A! With the Push Button 21 „AUXILARY CONTACT“ the contact can be manually switched on or off independent of programming and the operating situation. The LED 5 “Contact active” show the state of the contact. The drawing up the screw terminal “AUX CONTACT” is the inactive position mode, LED 5 “Contact active” off.
STUDER INNOTEC COMPACT 4.11 The Temperature sensor Operating voltage of lead-acid batteries change depending on the temperature. To correct the operating voltages according to the actual temperatures, a temperature sensor can be connected to the COMPACT. The compensation through the sensor is –3mV/°C/Cell. Order Number: CT-35 Dimensions: H x B x T / 58 x 51.5 x 22mm 5 Programming: 5.1 Standard setting The COMPACT is delivered with the default setting following: 5.1.
STUDER INNOTEC COMPACT 5.3.2 Set the voltage and timing threshold The programming is done in accordance with the following steps: Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for minimum 2 seconds simultaneously. With the Push Button 20 (select) select with of the battery level and the absorption time to be changed.
STUDER INNOTEC 5.4.3 COMPACT Example 5.4.3.1 Auxiliary Contact as generator starter When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is used as a condition, then you must take note of the following requirements. If you have to start an emergency back-up supply with a battery having a certain residual capacity, then two battery levels must be programmed. The first (i.e. Battery 25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e.
STUDER INNOTEC 5.5.1 COMPACT Diagram of the different mode Show an off LED Show a blinking LED Show a lighted LED 9 AC IN 1 CHARGER 2 AC IN 1 CHARGER 2 AC IN 1 CHARGER 2 AC IN 1 CHARGER 2 7 7 7 7 8 AC OUT 9 INVERTER 8 AC OUT 9 INVERTER 8 AC OUT 9 INVERTER 8 AC OUT 9 INVERTER All the functions are enabled. This is the factory setting. The inverter is disabled. Only the transfer switch and the charger will work normally. Charger and transfer switch are disabled.
STUDER INNOTEC COMPACT 8 Technical Data Type C1312 C2324 C3548 Inverter Nominal battery voltage Input voltage range Nominal power (W) Maximum power 30 min Maximum power 3min. Maximum power 5 sec Maximum load Asymmetrical load max. Standby adjustable Cos ϕ Maximum efficiency Power OFF, Standby, ON Power normal working no load Output voltage Output frequency quartz controlled Maximum distortion Dynamic behaviour 0 → 100 % Overload and short circuit protection Overheating temperature protection 12V 9.