Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information Read this manual carefully before commencing installation. This manual covers the following products: Monsoon S2.0 bar Single Monsoon S1.5 bar Twin Pt. No. 46497 Pt. No. 46506 Monsoon S3.0 bar Single Monsoon S2.0 bar Twin Pt. No. 46419 Pt. No. 46415 Monsoon S4.5 bar Single Monsoon S3.0 bar Twin Pt. No. 46420 Pt. No.
PRODUCT DESCRIPTION Electric motor driven single or twin ended peripheral pump, complete with an automatic control system, consisting of flow switches and electronic controls. APPLICATION Monsoon Standard pumps are suitable for positive head installation conditions. The pumps are designed for pressure boosting applications in vented stored hot or cold, clean fresh water systems, where under gravity, some flow (approx. 0.6 l/min) is available.
CHECKLIST IMPORTANT: With the pump removed from its packaging check for any damage prior to installation. If any damage is found contact Stuart Turner Ltd within 24 hours of receipt. B A Fig. 1 Item Description A Pump Qty Item Description B 1 Hose & sealing washer Qty 4 (2) Your product may vary slightly from the picture above. The quantities shown above are for twin pumps, (single pumps are shown in brackets). Cont ...
1 READ BEFORE COMMENCING PUMP INSTALLATION A. Water storage capacity. 1.11 The hot and cold water storage capacity must be sufficient to meet the flow rates required by the pumped equipment and any other water using fittings and appliances, which may be operated simultaneously. 1.12 Ensure the pump is primed as described in the priming section before starting, damage to the shaft seal will result otherwise. See Section 5 - Commissioning. B.
2 LOCATION - GENERAL 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.25 2.11 Access: For emergencies and maintenance the pump must be easily accessible. 2.12 Protection: The pump must be located in a dry position, frost free and protected from freezing, particularly when installed in a loft (not recommended). 2.13 Ventilation: Ensure an adequate air flow to cool the pump. Separate the pump from other appliances that generate heat. An 80 mm (3 “) air gap must be maintained around the pump. 2.
Fig. 2 (Twin Pump) least preferred area 200 mm min hot water services 350 mm min hot water services Fig. 3 (Single Pump) 350 mm min least preferred area Max. inlet head 14 m Min. inlet head 0.5 m 200 mm min Max. inlet head 14 m Min. inlet head 0.5 m 2.26 Non-Preferred Pump Location: The pump must be located with at least 0.5 metres flooded suction at all times.
Max. static inlet pressure 14 m 2 LOCATION - TWIN PUMP Outlet head must be below bottom of cold water tank and able to pass a minimum of 0.6 l/min of gravity flow Positive Duty Twin Pump System Fig. 5 Cold water connection: 2.27 The cold water supply: Must be a DEDICATED AIR FREE supply via a tank connector, and must be positioned at a slightly lower level (25 mm minimum) than the feed pipe to the hot water cylinder. Do not connect to the mains. 2.
Hot water connection: (Applicable to S1.5, S2.0, S3.0 and S4.0 bar Twins, S2.0, S3.0 and S4.5 bar Singles) 2. 29 Hot water cylinder or storage tank: When a hot water cylinder or storage tank is used, ensure the pipework size from the cold water storage to the hot water storage is of adequate size and a minimum of 22 mm for all models except the S4.5 bar twin which should be a minimum of 28 mm. 2.
3 PUMP CONNECTIONS Do not use stainless steel, chrome or nickel plated pipe with the flexible hose push-in plumbing connections. Do not introduce solder flux into the joint or surrounding area as connectors will be attacked and may fail. All solder joints should be completed and flux residues removed before final connection to push-in connections, on the flexible hose.
3.12 Hose to pipework: 1. The hoses are fitted with plastic push-in connectors, which must only be connected with the following: a) 22 mm diameter copper pipe to BS EN 1057 - R250 (half hard) - Table 3. b) 22 mm plastic pipe to BS 7291 part 1 and part 2 (Table 1), or part 3 (Table 1) plus internal support sleeve*. * The internal bore of the plastic pipe must be supported against collapse with the pipe manufacturers recommended support sleeve (pipe insert).
5. To break the joint, push pipe firmly into fitting, hold collet down and gently remove pipe. If the system has been filled with water care should be taken to isolate pump and towels used to absorb spilled water. 3.13 Typical Low Level Installation: In certain installations it may be necessary to install a 90° bend on the inlet or outlet connections of the pump before the flexible hose to accommodate a low level installation. Below are some preferred connection options.
4 ELECTRICAL INSTALLATION / EARTHING 4.11 Regulations: The electrical installation must be carried out in accordance with the current national electrical regulations and installed by a qualified person. 4.12 Safety: In the interests of electrical safety a 30 mA residual current device (R.C.D. not supplied) should be installed in the supply circuit. This may be part of a consumer unit or a separate unit. 4.13 Before starting work on the electrical supply ensure power supply is isolated. 4.
The wire which is coloured blue must be connected to the terminal which is marked with the letter N or coloured black. The wire which is coloured brown must be connected to the terminal which is marked with the letter L or coloured red. 4.21 Wiring Diagrams: Parallel wiring of two single pumps is not recommended.
4.24 Cable Gland Fitting Instructions: 1 2 Fig. 14 To enable correct assembly of the cable gland the ‘O’-ring (Fig. 14 item 1) must be placed over the cable before the clamping insert (Fig. 14 item 2) can be tightened. Note: Cable diameter range:- 6.5 mm to 9.5 mm. 4.25 Supply Cord Extension: The pumps are fitted with a supply cord to the following specification:All models . . . . . . . . . . . . . . . . . . HO5VV-F3 G 0.75 mm² - 6 Amp rated cable.
5 COMMISSIONING 5.11 System Flushing: This pump incorporates push-in connectors and plastic components that must not come into contact with solder flux, acid-based descalents or aggressive cleaning agents. The pipework system should be flushed out prior to the pump being connected to ensure any contaminants/chemical residues and foreign bodies are removed from elsewhere in the system. 5.12 Water Supply: Always ensure that water storage capacity is adequate to meet the demand.
6 MAINTENANCE 6.11 Turn off water supplies to the pump and release pressure by opening water outlets before attempting maintenance. 6.12 Inlet strainer: The inlet strainers may require periodical cleaning. The frequency of this operation is dependent upon installation conditions. The strainer is located in the inlet assembly of the pump casing (Fig. 15) and is removed as follows:a) Isolate pump electrically. b) Release all system pressure.
6.13 No other routine maintenance is required. 6.14 Water scale: As water is heated scale deposits are released in areas of hard water, scale can cause the mechanical seal to stick if left without use for long periods. The pump must be run for at least 5 minutes every four weeks to “exercise” all working parts. Run on cool water. See Section 7 - Technical Specification for note on water temperature. This particularly applies to guest bathrooms used infrequently. 6.
7 TECHNICAL SPECIFICATION (Single Models) Pump Dimensions Mechanical Electrical Model S2.0 bar Single S3.0 bar Single S4.5 bar Single Power supply Volts/phase freqency 230/1/50 230/1/50 230/1/50 Enclosure IPX4 IPX4 IPX4 Type of motor Induction Induction Induction Power consumption 245 Watts 385 Watts 555 Watts Full load current 1.1 Amps 1.7 Amps 2.4 Amps Rating Continuous (S1) @ 9 l/min & above Continuous (S1) @ 9 l/min & above Continuous (S1) @ 9 l/min & above Max.
7 TECHNICAL SPECIFICATION (Twin Models) S1.5 bar Twin Pump Dimensions Mechanical Electrical Model S2.0 bar Twin S3.0 bar Twin S4.0 bar Twin S4.5 bar Twin Power supply Volts/phase freqency 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Enclosure IPX4 IPX4 IPX4 IPX4 IPX4 Type of motor Induction Induction Induction Induction Induction Power consumption 345 Watts 425 Watts 640 Watts 890 Watts 1090 Watts Full load current 1.5 Amps 1.9 Amps 2.8 Amps 4.0 Amps 4.
8 TROUBLE SHOOTING GUIDE Symptoms Probable Cause Recommended Action Pump will not start. Insufficient gravity flow. Check flow rate minimum of 0.6 l/min required on full hot and cold. Electrical. Check power supply. Check fuse (see fuse section). Check circuit breaker is set. Check wiring connections. Pump jammed. If motor ‘Buzzes’ switch off power and contact Stuart Turner. Integral motor thermotrip activated.
8.11 Flow Switch Circuit Test: 1. First confirm visually that the flow switch reed clamps have not been dislodged during handling or installation. The clamps must be fully located within their flow switch body groove as shown. 2. To carry out the following test you will need to obtain a magnet, a typical fridge magnet is suitable. 3. Ensure the power supply is switched on. 4. Position the magnet directly in front of the reed clamp as shown.
9 THE MONSOON GUARANTEE Congratulations on purchasing a Stuart Turner pump. We are confident this pump will provide many years of trouble free service as all our products are manufactured to the very highest standard. All Monsoon Pumps are guaranteed to be free from defects in materials or workmanship for 3 years from the date of purchase.
In the event of a claim please telephone ‘PumpAssist’ or return the pump and flexible hoses with the accessories removed e.g pipes etc. If you have any doubt about removing a pump, please consult a professional. 0844 98 000 97 Proof of purchase should accompany the returned unit to avoid delay in investigation and dealing with your claim. You should obtain appropriate insurance cover for any loss or damage which is not covered by Stuart Turner Ltd in this provision. Please record here for your records.
DECLARATION OF CONFORMITY 2006/42/EC BS EN ISO 12100-1, BS EN ISO 12100-2, BS EN 809 2006/95/EC BS EN 60335-1, BS EN 60335-2-41 2004/108/EC BS EN 55014-1, BS EN 55014-2, BS EN 55022, BS EN 61000-3-2, BS EN 61000-3-3, BS EN 61000-4-2, BS EN 61000-4-3, BS EN 61000-4-4, BS EN 61000-4-5, BS EN 61000-4-6, BS EN 61000-4-11 1999/519/EC BS EN 62233 2011/65/EU IT IS HEREBY CERTIFIED THAT THE STUART ELECTRIC MOTOR DRIVEN PUMP AS SERIAL NUMBER BELOW, COMPLIES WITH THE ESSENTIAL REQUIREMENTS OF THE ABOVE E.E.C.