Vogue Installation User Instructions

15
Installation Checklist
2. Essential Information
GENERAL
Model:
Vogue
Vogue
Nominal Heat Output Wood kW 5.0
Efficiency Wood % 81
CO @ 13% O
2
Wood % 0.13
Weight Wood Kg 70
Recommended Fuels
Wood
Seasoned Wood (less than 20% moisture content)
As tested to the requirements of EN 13240 for intermittent operation
Flue/Chimney Size
May be reduced to 128mm (5") if burning approved
smokeless fuels or burning wood in an appliance
approved for use in a DEFRA smoke control area
Without flue liner Round (Diameter)
mm
153
inch
6
Without flue liner system (Square)
mm 135
inch 5
1
/
2
FLUES
With Liner of Factory made system (diameter)
installed in accordance with manufacturers
instructions
mm 150
inch 6
Flue/Chimney
minimum height**
All products
**must be 4.5m from the hearth to the top of the
flue, with no horizontal sections and a maximum of
4 bends. Bends must have angles of less than 45
degrees from the vertical.
m 4.5
feet 13
Flue Draught
Min
mm Wg
1.0
Nominal 1.5
Max 2.0
Flue Gas Mass Flow Wood g/s 7.1
Flue Gas Temperature at Spigot/Socket Wood
o
C
269
Flue Outlet Size
(Top or Rear Option)
All
mm 128
inch 5
European Min Spec for Chimney Flue - T400 N2 D 3 G50
VENTILATION
A) Traditionally Built Homes
• Where leakage is greater than 5m
3
/hour/m
2
.
• Ventilation normally required = 550mm
2
per kW output over 5kW
B) Modern Construction Homes
• Where leakage is less than 5m
3
/hour/m
2
.
• Ventilation normally required = 550mm
2
per kW
A Additional Ventilation
mm2 None
cm2 None
in2 None
B Additional Ventilation
mm2 2750
cm2 27.5
in2 4.4
For full technical details on ventilation see Technical Appendix on Page 34
In the U.K. Additional information covering the
installation of the appliance may be found in the
following British Standards: BS EN 15287,
BS6999, BS8303.