Vogue Wall Mounting Kit Installation Instructions

3
Non-Combustible Materials
2.2 All appliances will require some clearance between them and any non-combustible materials to allow for either:
— Installation, servicing or accessing controls.
— Convection in order for the appliance to function properly.
Recommended: Minimum clearances for installation/servicing/convection is:
Bottom - 100mm Sides - 50mm Top - 100mm
NOTE: If the non-combustible surface is less than 200mm thick additional clearances may be required.
This requirement ensures that the non-combustible material does not transmit excessive heat through the wall onto combustible
material which might be placed against it.
See Diagrams 2 and tables.
Combustible Materials
ONLY MOUNT TO A NON-COMBUSTIBLE SETTING CAPABLE OF SUPPORTING THE WEIGHT OF THE APPLIANCE.
CONSULT A SUITABLY QUALIFIED PERSON IF NECESSARY.
2.3 It is essential for safety to ensure the following clearances to combustible materials are maintained, see Diagram 2.
Note: Minimum distance to combustible material must be 450mm from any exposed single wall flue pipe.
Follow Flue manufacturer's instructions.
(Some single skin flue manufacturer's do not state distances to combustibles.
As a rule of thumb use 3 x the diameter of the flue to calculate the distance.)
General Information
2
200mm THICK
NON-COMBUSTIBLE
300mm Minimum
Non-Combustible
150mm
Minimum
12mm
1200mm
Minimum
(or 300mm
above stove)*
NOTE: Only use
approved xings
MINIMUM 840mm
NON-COMBUSTIBLE
COMBUSTIBLE WALL
(NOT EXTENDING TO
FRONT OF STOVE)
420mm
210mm 210mm
*Height of appliance + 300mm OR 1200mm from the hearth (take largest dimension)
**If the appliance is installed in an elevated setting it is recommended to increase the hearth
depth to safely contain any falling logs or embers. The higher the appliance is installed, the
deeper the hearth should be.
A
A
Single Wall 225
225mm**
Minimum