Studio Freestanding Installation User Instructions

37
3. Ventilation
3.1 Many older buildings are sufficiently ventilated by natural
leakage of air to provide suitable air supply for an
appliance of 5kW output or less.
Modern building techniques have reduced the amount of
air that leaks in or out of a house. A modern construction
with an air tightness of less than 5m
3
per hour per m
2
requires an air vent for ALL solid fuel appliances including
those with a rated heat output of less than 5kW.
NOTE: The air leakage of a modern house is tested at
the completion of construction and a certificate issued
confirming this.
3.2 This appliance requires a constant supply of air to maintain
proper combustion and effective flue performance.
3.3 An inadequate air supply can result in poor combustion
and smoke entering the room which is potentially
dangerous.
3.4 This supply of air can come from either:
Purpose provided ventilation.
Some Stovax appliances can also be fitted with an
optional outdoor air kit which allows air to be drawn in
from the outside.
3.5 The amount of air required must comply with local
building regulations and the rules in force.
3.6 If spillage is detected during commissioning then there
may be insufficient natural ventilation and an additional air
supply will be necessary.
3.7 Permanent air vents should be non-adjustable and
positioned where they are unlikely to be become blocked.
3.8 If vents open into adjoining rooms or spaces there must be
an air vent of at least the same size direct to the outside.
3.9 Site the vents where cold draught is unlikely to cause
discomfort. This can be avoided by placing vents near
ceilings or close to the appliance (See diagram).
3.10 Extractor fans or cooker hoods must not be placed in the
same room or space as this can cause the appliance to
emit fumes into the room.
3.11 Increase air supply provisions where a room contains
multiple appliances.
3.12 If any checks reveal problems do not proceed with the
fitting of the appliance until they have been rectified.
Well ventilated
roof space
Living room
(example)
Hall
Well ventilated space
Suspended floor
Combustion
appliance
4. Minimum Dimensions - Hearth
4.1 The appliance must stand on a non-combustible
constructional hearth which is at least 125mm thick with the
minimum dimensions as shown in diagram.
As this appliance can be installed in an elevated setting it is
recommended to increase the 225mm hearth depth to safely
contain any falling logs or embers. The higher the appliance
is installed the deeper the hearth should be to protect the
floor.
4.2 The building must have a suitable load-bearing capacity for
the hearth and appliance. Consult a structural engineer for
advice before proceeding.
4.3 When fitting into an existing hearth check that the appliance
complies with current construction regulations and is at least
the minimum sizes shown.
4.4 If there is no existing fireplace or chimney it is possible to
construct a suitable non-combustible housing and hearth
setting. The flue must be installed in accordance with all
local and national regulations and current rules in force.
4.5 Check if adding a new chimney to your property requires
planning permission.
4.6 Some houses are built using a timber frame construction
with high levels of thermal insulation. Isolate the appliance
from combustible materials, and provide sufficient ventilation
to maintain the heating efficiency.
Technical Appendix - Ventilation