Studio Freestanding Installation User Instructions

17
Installation Checklist
Non-Combustible Materials
4.2 All appliances will require some clearance between them
and any non-combustible materials to allow for either:
— Installation, servicing or accessing controls.
— Convection in order for the appliance to function properly.
Minimum clearances for installation/servicing/convection is:
Rear - 25mm Sides - 50mm Top - 100mm
NOTE: If the non-combustible surface is less than
200mm thick additional clearances may be required.
This requirement ensures that the non-combustible material
does not transmit excessive heat through the wall onto
combustible material which might be placed against it.
See Diagrams 4 & 5 (Fireplaces)& Diagram 6
(Freestanding) and table below.
Distance to Non-combustible Materials
Distance of
Appliance to Wall
(A)
Minimum
Thickness of wall
(B)
Minimum Height of
Wall (C)
0mm - 50mm* 200mm Height of appliance
+ 300mm OR
1200mm from the
hearth (take largest
dimension)
51mm - 300mm 75mm
300mm+ No requirement No requirement
Freestanding Installation
6
C
B
A
A
150
150
Non Combustible Material
Combustible Materials
4.3 It is essential for safety to ensure the following clearances to
combustible materials are maintained.
See Diagrams 4 & 5 and table below.
Model A (side) E (Rear)* D (Above)
Studio 500 300 300 N/A
Studio 1 300 500 N/A
Studio 2 300 700 N/A
Studio 3 300 450 N/A
* Note this distance can be reduced by the fitting of a heat
shield kit, check with your Stovax retailer for availability and
clearances.
5. Smoke Control Kit
This section applies to the Studio products listed:
Product Code Appliance
RVFST-500 Studio Freestanding 500
RVFST-1HT Studio Freestanding 1
RVFST-2HT Studio Freestanding 2
5.1 TheStudiomodelslistedaresuppliedwithapre-ttedsmoke
control kit and have been independently tested to PD6434
making them exempt from the controls that generally apply
in Smoke Control Areas.
5.2 These models are suitable for use in a Smoke Control Area
when burning wood and following the instructions for use
speciedinthismanualbutONLYiftheSmokeKithasnot
been removed.
5.3 Iftted,theSmokeControlkitcanbeseeninthefollowing
locations, see Diagrams 7 & 8.
7
Airwash
Frame
Glass
Airwash
Restrictor
Gap between Inner
and Outer box