2.4 Electronic trip unit ETU600
3WA Air Circuit Breakers
Equipment Manual, 05/2021, 92310000002-03
97
2.4.5.2 Enhanced protective functions EPF parameters
In addition to the two sets of protection parameters A and B, enhanced protective functions
are optionally available for the ETU600 electronic trip unit.
Parameters Setting range Condition Basic
setting
Unbalance
Current unbalance
1)
Can be switched on/off
Off
Setting
5 … 50%
50%
Tripping time
0 … 15 s
0 s
Voltage unbalance
2)
Protective function can be
enabled/disabled
Off
Setting
5 … 50%
50%
Tripping time
0 … 15 s
0 s
Harmonic analysis
THD current
1)
Can be switched on/off
Off
Setting
3 … 50%
50%
Tripping time
5 … 15 s
5 s
THD voltage
2)
Can be switched on/off Off
Setting
3 … 50%
50%
Tripping time
5 … 15 s
5 s
Voltage
Undervoltage U
LL
Can be switched on/off
Off
Setting
100 … 1100 V
100 V
Tripping time
0 … 15 s
0 s
Overvoltage U
LL
Can be switched on/off Off
Setting
200 … 1200 V
1200 V
Tripping time
0 … 15 s
0 s
Undervoltage ULN
Can be switched on/off
Off
Setting
60 ... 600 V
100 V
Tripping time 0 … 15 s 5 s
Overvoltage U
LN
Can be switched on/off
Off
Setting
120 ... 690 V
690 V
Tripping time
0 … 15 s
0 s