Datasheet
STPMC1 Theory of operation
Doc ID 15728 Rev 7 25/77
If the counted number of f
MCLK
/8 pulses between two trailing edges of
LIN
is lower than the
2
16
equivalent pulses, the base frequency exceeds the upper limit. In this case, such error
must be repeated three times, in order to set the error flag
BFR
, as shown in
Figure 10
.
The in-band base frequency resets the flag
BFR
. If
BFR
is cleared, the measured period
value is latched, otherwise a default value of period is used as a stable data to compute
frequency needed to adapt the decimation filter and to perform frequency compensation of
reactive energy and RMS current I
X
in case of non Rogowski current sensor.
The
BFR
flag is also set if the register value of the RMS is too low. In this case also the
status bit
LOW
is set.
The condition for setting
LOW
and consequently
BFR
of each phase is U
X
< U
Xmax
/32
(U
Xmax
= 2
12
) it means if the U
X
register drops below 128
LOW
and
BFR
are cleared when
the register value goes above 256 (U
X
> U
Xmax
/16).
BFR
, then, gives also information about
the presence of the line voltage.
When the
BFR
error is set, the computation of power is zero and the energy registers
(active, reactive and fundamental) are blocked, unless single wire mode operation is entered
(see
Section 9.7
).
When the MOP, MON and LED pins are configured to provide the pulsed energy information
they are held low if
BFR
is set.
The 3-ph status bit
BFF
is the OR of each phase bit
BFR
.
9.7 Single wire operation mode: SWM (status bits:
NAH
,
BFR
,
configuration bit FRS
)
The STPMC1 supports single wire meter (SWM) operation. In this condition, since there is
no voltage information, the current RMS values, instead of the energies, are accumulated in
20-bit dedicated registers located in ACR, ACS, ACT (20-bit accumulator of RMS I
X
per hour
[Ah]).
Figure 10.
LIN
and
BFR
behavior when f
line
> f
MCLK
/2
16