INSTALLATION
Installation
11.4.3 Connection with external signal transmitter
The appliance can be connected to an external signal in addition
to the standard connection. Two wires with a 240 V potential must
be connected to terminals X3/2 & X3/1. The X3 connection does
not carry a significant load, and only provides an on/off signal to
the appliance.
When this signal is active, the appliance will operate to satisfy
the secondary setpoint instead of the primary. See 5.2.5, “Set
temperature2”, pg. 14 for more information.
Following activation of the external signal (the external signal is
present for at least one minute), set temperature 2 activates for
at least 20 minutes.
GND
L
L
GRN
BK 1
BK 2
N
L
11.4.4 Connection with off-peak and external signal
transmitter
The appliance can be operated in a mode combining the external
signal and the off-peak power connection. This mode would re-
quire the two load connections on the X0 terminal block and the
potential-free signal on the X3 terminal block.
GND
L
L
GRN
BK 1
BK 2
L
L
N
L
Interruptible
power supply
Note
f Never wire up terminal X3/1.